DFLEX Assembly instructions |
50
7. Connection of the drainage
The following optional elements have a condensate or spillage collection tank:
•
Pre-cooling battery
•
Pre-heating battery
•
Post-cooling battery
•
Post-heating battery
•
Heat exchanger
The outlet pipe of the tank must be connected to the drainage network:
Connect the drainage network to the common outlet (optionally, a cut-valve can be
installed before the siphon):
•
The connection of the water outlet to the drain must have a siphon or water seal
of sufficient height (2H) to exceed the system pressure and ensure the basin is
emptied completely for hygiene reasons. The system will also have the normal
inclin
ation of any drain line. See detail “A” page 51.
•
The siphon must be able to drain freely and must not have direct access to the
sewer pipe.
•
Recovering water from condensates or spills due to breakage in the drinking
water network is totally prohibited.
Summary of Contents for DFLEX 1100
Page 2: ...DFLEX Assembly instructions 2...
Page 16: ...DFLEX Assembly instructions 16 The following result is obtained...
Page 29: ...DFLEX Assembly instructions 29 DFLEX 1100 400V 5...
Page 30: ...DFLEX Assembly instructions 30 DFLEX 1100 440 480V NOT WIRING...
Page 31: ...DFLEX Assembly instructions 31 DFLEX 1300 400V 5...
Page 32: ...DFLEX Assembly instructions 32 DFLEX 1300 460V 5 NOT WIRING...
Page 33: ...DFLEX Assembly instructions 33 DFLEX 1700 400V 5...
Page 34: ...DFLEX Assembly instructions 34 DFLEX 2100 400V 5...
Page 35: ...DFLEX Assembly instructions 35 DFLEX 2100 460V 5 48 Elementos NOT WIRING...
Page 36: ...DFLEX Assembly instructions 36 DFLEX 2100 460V 5 45 elements Requires SSR in E4 NOT WIRING...