7.4.3 Heating Mode
7.4.3.1 Compressor running rules
When T1-Ts>ΔT, the compressor will stop,
when T1-T
S
<ΔT-1.5 the compressor will be on.
ΔT is the programmed parameter of temperature compensation.
When the current is more than setting value,the current protection function will be activated and the
compressor will stop.
7.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units,the fan speeds are different
T 4
E
D
C
B
A
A +
7.4.3.3 Indoor fan running rules
When the compressor is on, the indoor fan can be set to high/med/low/auto.
When indoor unit coil temp. is low, the anti-cold air function will start and indoor fan motor will run at
low speed, the speed can’t be changed ,when the temp. is lower than setting value, the indoor fan
motor will stop.
When the indoor temp reaches the setting temp., the compressor will stop, the indoor fan motor will
run at the minimum speed or setting speed.(The anti-cold air function is valid).
The indoor fan is controlled as below:
Summary of Contents for FSAI-SU-120AE2
Page 12: ...12 4 2 Wiring Diagram Indoor unit FSAI SU 90AE2 FSAI SU 120AE2 Outdoor unit FSOAI SU 90AE2 ...
Page 13: ...13 Outdoor unit FSOAI SU 120AE2 ...
Page 45: ...45 8 2 6 Refrigerant Leakage Detection diagnosis and solution EC ...
Page 46: ...46 8 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 47: ...47 8 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 48: ...48 8 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 49: ...49 8 2 10 Inverter compressor drive error diagnosis and solution P4 ...