INSTALLATION: 

The installation of this heater for use with natural gas shall conform with local codes or, 
in the absence of codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 and 
the Natural Gas and Propane Installation Code, CSA B149.1. 
 
The installation of this heater for use with propane tank or cylinder shall conform with 
Local codes or, in the absence of local codes, with the Standard for the Storage and 
Handling of Liquefied Petroleum Gases, ANSI/NFPA 58 and the Natural Gas and 
Propane Installation Code, CSA B149. 
 
This heater must be located at least 10ft (3m) from any propane gas cylinder. This 
heater shall not be directed toward any propane gas container within 20ft (6m). 
 

CLEARANCE TO COMBUSTIBLES: 
 

F-1500T  

 

TOP: 4 ft  

   FRONT: 16 ft  

SIDES: 2 ft        REAR: 2 ft 

 

 
CONNECTING THE CYLINDER: 
 

If cylinders are used to supply the heater, no cylinders smaller than 100lb capacity shall 
be used. These cylinders must supply a vapor withdrawal only. 
 
1.  

All cylinder connections must be made using a wrench to tighten the POL     
fitting. 

 
2.  

Be sure that the cylinder valve is in the closed position when connection 
or disconnecting the cylinder. 
 

3.  

A soap and water solution must be applied to all connections in order to leak 
check the system. 
 

The gas must be turned off at the propane supply cylinder(s) when the heater is not in 
use. When the heater is to be stored indoors, the connection between the propane 
supply cylinder(s) and the heater must be disconnected and the cylinders removed from 
the heater and stored in accordance with Standard for the Storage and Handling or 
Liquefied Petroleum Gases, ANSI/NFPA 58 and CSA B149.1, Natural Gas and Propane 
Installation Code. 
 

PIPING: 

This heater must be installed by a qualified gas technician following 

local codes published by the authority having jurisdiction. Sizing of 
supply piping must be determined using the length of pipe run as 
well as total btuh rating of the appliance(s). Appropriate piping 
tables must be used to determine size of supply piping dependant 
on the length of run from source. 

 

Summary of Contents for F-1000T

Page 1: ...ture reference For F 1000T DUAL FUEL CONSTRUCTION HEATER CERTIFIED FOR USE IN CANADA AND U S A As per Standard ANSI Z83 7 2000 CSA 2 14 2000 Gas Fired Construction Heaters Unvented Unattended Type FLAGRO INDUSTRIES LIMITED ST CATHARNIES ONTARIO CANADA ...

Page 2: ...OSION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING NOT FOR HOME OR RECREATIONAL VEHICLE USE WARNING INTENDED US...

Page 3: ... YOU HAVE QUESTIONS ABOUT APPLICATIONS Other standards govern the use of fuel gases and heat producing products in specific applications Your local authority can advise you about these SPECIFICATIONS Model Number F 1000T Input 1 000 000 btuh Fuel Natural Gas or Propane Inlet Pressure Natural Gas 7 0 W C Propane 11 W C Ignition Direct Spark Ignition Thermostat Control Air Circulation 7000 cfm Fuel ...

Page 4: ... vapor withdrawal only 1 All cylinder connections must be made using a wrench to tighten the POL fitting 2 Be sure that the cylinder valve is in the closed position when connection or disconnecting the cylinder 3 A soap and water solution must be applied to all connections in order to leak check the system The gas must be turned off at the propane supply cylinder s when the heater is not in use Wh...

Page 5: ...d depending on the fuel being used A fuel selector valve is located on the manifold of the heater Ensure that this valve is in the proper position depending on the fuel being used DO NOT operate the heater with the valve in the incorrect position HOSES All hoses used to connect this heater of fuel supply must be Type 1 approved propane natural gas hose assemblies ELECTRICAL WARNING Electrical Grou...

Page 6: ...t into operation The replacement hose assembly shall be that specified by the manufacturer 3 The appliance must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids 4 The flow of combustion and ventilation air must not be obstructed Be sure to check the fan assembly and ensure that the motor and blade are operating properly 5 Compressed air should be us...

Page 7: ...y 4 Open all gas supply valves 5 Depress the main switch to the START position The fan will start and the burner should ignite 6 Set the Thermostat to the desired temperature 7 If heater fails to ignite after 3 attempts call your supplier for service TO SHUT DOWN 1 Close the main gas supply valve while the heater is operating 2 Move the main switch to the OFF position 3 Disconnect the heater from ...

Page 8: ... turn counter clockwise to decrease sensitivity POSSIBLE CAUSE Blockage in copper inlet tubes REMEDY Disconnect tubes from air switch Use high pressure air to clean any debris that my block the airflow POSSIBLE CAUSE Faulty Switch REMEDY Replace Switch POSSIBLE CAUSE Rear of heater blocked REMEDY Ensure rear of heater is unobstructed and proper rear clearances are maintained see approval label ...

Page 9: ...ssures are supplied to the heater see approval label POSSIBLE CAUSE Spark Plug REMEDY Ensure gap in spark plug is approx 3 16 Check spark plug wire connections Ensure spark plug has good spark Replace spark plug if necessary POSSIBLE CAUSE Ignition Board REMEDY Ensure electrical signals for both spark plug and solenoid are present use volt meter Ensure ignition board is properly grounded POSSIBLE ...

Page 10: ...PROBLEM HEATER WILL NOT REMAIN LIT AFTER START UP POSSIBLE CAUSE Faulty flamerod wire REMEDY Check flamerod wire for any damage Ensure connections are secure Replace flamerod if necessary ...

Page 11: ...CTOR VALVE S 1003 FUEL SHUT OFF VALVE S 1003A IGNITOR S 408A FAN BLADE S 1001 PRESSURE ADJUSTMENT CAP FOR S 1002 REG S 1002C REGULATOR 1 2 PSI S 1002 S S FILTER SCREEN S 1002FS FLAME ROD S 406A FLAME ROD WIRE S 407A IGNITOR WIRE S 1009A OFF RUN START SWITCH S 411 BURNER S 1005 MAIN RELAY S 412 ...

Page 12: ...OARD S 415P AIR PROVEN SWITCH S 414 THERMOSTAT S 416 REAR SCREEN S 1019 8 RUBBER WHEELS S 1022 AIR SENSING TUBES S 1027 POWER CORD S 1021 CLEAR INDICATOR LIGHT S 1020A RED INDICATOR LIGHT S 1020B GREEN INDICATOR LIGHT S 1020C MOTOR MOUNT BRACKET S 1033 ...

Page 13: ...A IGNITION WIRE S 410 HIGH TEMPERATURE LIMIT S 411 OFF RUN START SWITCH S 412 MAIN RELAY S 414 AIR PROVING SWITCH S 415P POTTED IGNITION CONTROL 120V S 415W WIRING HARNESS S 416 THERMOSTAT S 1019 SCREEN ASSEMBLY S 1020A CLEAR INDICATOR LIGHT S 1020B RED INDICATOR LIGHT S 1020C GREEN INDICATOR LIGHT S 1021 POWER CORD INCLUDING PLUG S 1022 RUBBER WHEEL 8 ACCESSORIES B42R1 25 SECOND STAGE REGULATOR 1...

Page 14: ...000T WIRING DIAGRAM 2010 Note If any of the origional wire as supplied with the appliance must be replaced it must be replaced with type 14g TEW wire or its equivalent FLAGRO INDUSTRIES LIMITED V1 L1 V2 L2 S1 GND IGN FLAME ROD SPARK PLUG FENWAL IGNITION BOARD GROUND POTTED CONTROL BROWN BLACK YELLOW WHITE WHITE BLACK STRIPE PURPLE RED GREEN LIGHT SOLENOID VALVE SOLENOID VALVE ...

Reviews: