- 4 -
Liquefied Petroleum Gases, ANSI/NFPA 58 and CSA B149.00, Natural Gas and
Propane Installation Code.
PRESSURES:
MAXIMUM INLET PRESSURES:
LP:
14.0 IN. WC.
MINIMUM INLET PRESSURES:
LP:
11.0 IN. WC.
This heater must be supplied by pressures indicated on the
approval label. Over pressure may cause controls to fail.
DO NOT supply this unit with more than 11.0 in. W.C.)
FUEL:
This heater will operate on propane only. The manifold pressure is
listed on the approval label and the hose and regulator have been
provided. Any replacement parts must be purchased from the
manufacturer or authorized distributor.
HOSES:
All hoses used to connect this heater of fuel supply must be Type 1
approved propane / natural gas hose assemblies.
ELECTRICAL:
WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for
your protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle.
120v supply must be available. Please note that the motor on this
unit requires 20 amps. Ensure appropriate gauge extension cord is
used.
CLEARANCE TO COMBUSTIBLES:
TOP: 5 ft
FRONT: 2 ft
SIDES: 1 ft
REAR: 2 ft