Safety Directions
Compulsory declaration and recurring
inspection
Declaration of possession of cooling equipment must
be submitted to the local inspection authorities, in
most cases the Public Health and Environment
Authority in your municipality, if including this
cooling unit the total amount of refrigerant charged in
your operations amounts to more than 10 kg.
Recurring inspection
Recurring inspection, i.e. leakage searching of the refri-
gerant system that must be done at least once annually
by an accredited inspectorate (normally a refrigeration
service company), See under “Maintenance”.
EQKA Cooling unit
Fläkt Woods
8643 GB 2012.11
2
We reserve the right to alter specifications
Installation and Maintenance Instructions
Important!
– The unit must NOT be used for pur-
poses other than as a cooling unit.
– The cooling unit’s Operating & Main-
tenance Instructions must be studied
carefully before starting/ operating/
servicing/maintaining/scrapping
the unit.
Keep these instructions in a safe place
for future reference!
– All service and maintenance must be
carried out by a professional!
Service/maintenance of the cooling
system must only be carried out by an
accredited company and qualified
personnel wearing required protective
equipment (gloves and protective eye-
glasses).
– Automatic start! Open and lock the
main switch of the cooling unit before
beginning any work on the unit!
– Do NOT stand on the cooling unit!
– Use only genuine spare parts for
maintenance!
Neglect to comply with any of the
above terms can involve a serious
safety risk and nullify the guarantee/
product liability!
Size
Capacity
Nom. Cooling
Max.
Max.
(a)
Variant
Capacity
Current
Current
Circuit
Circuit
Circuit
Circuit
Total
(c)
(kW)
(A)
(A)
1
2
3
4
008
1
13
9,3
18,5
1,4
2,1
3,5
008
2
15,5
11,2
22
1,6
2,4
4
011
1
15,5
11,2
22
1,6
2,4
4
011
2
24,5
17,3
36,1
2,6
3,9
6,5
018
1
28
20
40,6
3,0
4,5
7,5
018
2
37,5
25,9
50,3
4,0
6,0
10
023
1
44
27,8
58,6
4,8
7,2
12
023
2
56
35,3
71,6
6,0
9,0
15
032
1
58,5
37,3
69,8
6,0
9,0
15
032
2
73,5
49,9
104,8
7,6
11,4
19
041
1
69
49
88
8,0
12,0
20
041
2
98,5
58,8
117,3
8,6
8,6
8,6
26
050
1
98,5
58,8
117,3
8,6
8,6
8,6
26
050
2
125,5
81
10,9
10,9
10,9
33
072
1
125,5
81
10,9
10,9
10,9
33
072
2
151
89,2
10,0
10,0
10,0
10,0
40
The fuse protection should be sized by a qualified electrician.
3 x 400 V
Technical Data - EQKA
3 x 230 V