Maintenance

LQQA Humidifier, for circulated water

Maintenance adjustments 

 

Water:

Determine the calcium and bicarbonate content and the 

pH value of the water. These values can be obtained 

from a water analysis or from the local water authority. 

Plot the values of bicarbonate, calcium and pH in chart
1 on page 5 to determine in which zone the water can

be classified. If the water is of zone 4 type, it should 

be softened.

Level monitors fig. 2

Level monitor A:   Level monitor A: Closes the water 

 

supply valve when the water  

 

 

reaches max. level A.

Setting A:  

65 mm from the upper edge of the  

 

water tray (sizes 60–84). 

Level monitor B:   Opens the drain valve for water

 

bleed-off.

Setting B:  

The zone value obtained (see page 5)

 

determines at which setting level

 

monitor B (Fig. 2) is to be preset. 

 

Level monitor C:   Stops the circulation pump and opens

 

the water supply valve if the water

 

level drops below level C.

Setting C:  

25 mm from the bottom of the water

 

tray (sizes 60–84) 

 

Level relays:

NR 1, NR 2 and NR 3 are shown in Fig. 7. The level

relays are preset at a sensibility of 40 kΩ. If softened

water is used and the level monitors don’t work, the

sensibility setting can be increased to 100 kΩ.

  1.  Control box, on the outside
  2. Control box, on the inside
  3. Shut-off valve (not included)
  4. Water filter, max. 500 mm mesh (not
  included)
  5. LQAZ-08 Water trap (accessory)
  6.  Water supply pipe
  7. Humidifier fill
  8. Droplet eliminator
  9. Spray pipe
10. Pump
11. Flow controller
12. Valve with motor actuator
13. Overflow hose
14. Water level sensor
15. Solenoid valve
16. Flushing hose
17. End plug
18. Side wall

17

18

3

2

4

16

15

14

1

9

7
8
10

11

12

13

5

6

Size  60-84

Fig. 1

1

2

3

ZON

A

B C

Zon

3
2
1

Level monitors

Zone Scale

Level monitor B: Adjustable

Adjusting screw

Fig. 2

Summary of Contents for LQQA

Page 1: ... at which setting level monitor B Fig 2 is to be preset Level monitor C Stops the circulation pump and opens the water supply valve if the water level drops below level C Setting C 25 mm from the bottom of the water tray sizes 60 84 Level relays NR 1 NR 2 and NR 3 are shown in Fig 7 The level relays are preset at a sensibility of 40 kΩ If softened water is used and the level monitors don t work th...

Page 2: ...evel in the tray reaches level monitor A that water bleed off can be done by manually opening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has drop ped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet v...

Page 3: ...ect a Time of 24 black digits Table 2 Presetting the time relay Table 3 Presetting time relay TR1 Size Time required for emptying Normal operation preset value High humidification over a long period Δx 8 gram Δx 5 gram 90 60 90 60 60 62 64 30 60 60 0 0 30 30 90 240 0 0 120 71 73 60 90 30 60 180 240 90 120 80 82 84 90 90 120 60 60 60 180 240 300 120 120 120 Range Time ETR4 69 A Function 1s 1 5 5 12...

Page 4: ...aken into account To ensure acceptable performance the concen tration of Cl in the fresh water must not exceed 50 mg l and that of Cu must not exceed 0 02 mg l To set the timer for emptying and flushing For normal function the timer should be preset to ON When emptying which can be programmed to occur once or several optional times every 24 hour period the timer will reset itself to the OFF settin...

Page 5: ...umbers on the display Choice of function Ex Auto Prog Pulse Cycle Delete The timer has also been preset for the following Summer and winter time in the country where it is to be used Date and time in the time zone where it is to be used Change of current time of day 1 Press menu 2 times flashes 2 Press OK Display shows YEAR change with or 3 Press OK Display shows MONTH change with or 4 Press OK an...

Page 6: ... m Max pH of aluminium Bikarbonate HCO 3 mg l P r e c i p i t a t i o n z o n e T r a n s i t i o n z o n e S a f e z o n e Determining the water quality zone The following particulars are required to be able to deter mine the water quality zone the pH of the water the bicarbonate concentration HCO3 mg l the calcium concentration Ca2 mg l This data can be obtained from a municipal water autho rity...

Page 7: ... tray guide rails or electric cables E Thefillsarerelativelyfragileandthereforeshould betreatedwithgreatcare Cleanbysprayingwitha jetofcleanwater possiblycontainingtheULCZ 01 cleaning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the spacer plate and close the door To clean ...

Page 8: ... 12 Bleed off Level relay Maintains correct level Level relay L3 L2 L1 2 1 0 1 3 4 5 6 PE I I I 1 5 3 2 4 6 W U V 3 M 2 1 F1 HB Q1 Q2 K1 K2 CP1 CP2 6 4 2 5 3 1 N N SU1 A2 A1 Timer Emptying Flushing 6A A2 A1 R1 Auxiliary relay Emptying Flushing SU1 4 3 5 TF c no 1 2 CP1 Contactor A2 A1 K1 GM c no 3 4 15 16 18 15 18 16 15 18 16 MV1 11 12 Solenoid valve Valve actuator SV1 13 15 14 3 2 1 NR1 A1 A2 B1 ...