background image

 Fläkt Woods 

9206 GB 2011.11 

4

 

Specifications are subject to alteration without notice

Maintenance

LQQA Humidifier, for circulated water

Water quality

Evaporation causes an increase in the concentration of

minerals in the circulating water, which necessitates

continuous bleed-off and make-up with fresh water.

The bleed-off rate is dependent on factors such as:

■ 

the pH of the water

■ 

the bicarbonate concentration (HCO3 ), mg/l

■ 

the calcium concentration (Ca2+), mg/l

This data can be obtained from a municipal water autho-

rity or by analysing the water.

Lime precipitation can be prevented by plotting the per-

tinent data in Chart 1 on page 4 to determine the current

risk zone. Water level monitor B can then be set according

to the relevant zone. If the water is too hard, it may be 

necessary to subject it to partial softening.

In addition to the risk of lime precipitation, the concentra-

tion of chlorine (Cl) and copper (Cu) must be taken into 

account. To ensure acceptable performance, the concen-

tration of Cl in the fresh water must not exceed 50 mg/l 

and that of Cu must not exceed 0.02 mg/l.

To set the timer for emptying and flushing

For normal function, the timer should be preset to

”ON”. When emptying, which can be programmed to

occur  once  or  several  (optional)  times  every  24-hour 

period, the timer will reset itself to the ”OFF” setting 

for 10 minutes. After that, the timer will reset itself to 

”ON” for 2 minutes to allow flushing.

  The timer will then reset itself to the ”OFF” setting 

for 3 minutes for additional emptying before resetting 

itself back to ”ON” for normal operation.

  In  the  following  example,  emptying  and  flushing 

are required once every 24 hours from 12.00 to 12.15 as

scheduled below.
Period  

Timer setting   Activity

 

00.00–12.00  

ON  

Normal operation

12.00–12.10  

OFF  

Emptying

12.10–12.12  

ON  

Flushing

12.12–12.15  

OFF  

Additional emptying

12.15–24.00  

ON  

Normal operation

This can be done most easily by programming the ope-

ration times from 12.15 to 12.00 and from 12.10 to 12.12

on  a  daily  basis!  Emptying  and  additional  emptying 

will then occur from

Summary of Contents for LQQA

Page 1: ... at which setting level monitor B Fig 2 is to be preset Level monitor C Stops the circulation pump and opens the water supply valve if the water level drops below level C Setting C 25 mm from the bottom of the water tray sizes 60 84 Level relays NR 1 NR 2 and NR 3 are shown in Fig 7 The level relays are preset at a sensibility of 40 kΩ If softened water is used and the level monitors don t work th...

Page 2: ...evel in the tray reaches level monitor A that water bleed off can be done by manually opening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has drop ped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet v...

Page 3: ...ect a Time of 24 black digits Table 2 Presetting the time relay Table 3 Presetting time relay TR1 Size Time required for emptying Normal operation preset value High humidification over a long period Δx 8 gram Δx 5 gram 90 60 90 60 60 62 64 30 60 60 0 0 30 30 90 240 0 0 120 71 73 60 90 30 60 180 240 90 120 80 82 84 90 90 120 60 60 60 180 240 300 120 120 120 Range Time ETR4 69 A Function 1s 1 5 5 12...

Page 4: ...aken into account To ensure acceptable performance the concen tration of Cl in the fresh water must not exceed 50 mg l and that of Cu must not exceed 0 02 mg l To set the timer for emptying and flushing For normal function the timer should be preset to ON When emptying which can be programmed to occur once or several optional times every 24 hour period the timer will reset itself to the OFF settin...

Page 5: ...umbers on the display Choice of function Ex Auto Prog Pulse Cycle Delete The timer has also been preset for the following Summer and winter time in the country where it is to be used Date and time in the time zone where it is to be used Change of current time of day 1 Press menu 2 times flashes 2 Press OK Display shows YEAR change with or 3 Press OK Display shows MONTH change with or 4 Press OK an...

Page 6: ... m Max pH of aluminium Bikarbonate HCO 3 mg l P r e c i p i t a t i o n z o n e T r a n s i t i o n z o n e S a f e z o n e Determining the water quality zone The following particulars are required to be able to deter mine the water quality zone the pH of the water the bicarbonate concentration HCO3 mg l the calcium concentration Ca2 mg l This data can be obtained from a municipal water autho rity...

Page 7: ... tray guide rails or electric cables E Thefillsarerelativelyfragileandthereforeshould betreatedwithgreatcare Cleanbysprayingwitha jetofcleanwater possiblycontainingtheULCZ 01 cleaning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the spacer plate and close the door To clean ...

Page 8: ... 12 Bleed off Level relay Maintains correct level Level relay L3 L2 L1 2 1 0 1 3 4 5 6 PE I I I 1 5 3 2 4 6 W U V 3 M 2 1 F1 HB Q1 Q2 K1 K2 CP1 CP2 6 4 2 5 3 1 N N SU1 A2 A1 Timer Emptying Flushing 6A A2 A1 R1 Auxiliary relay Emptying Flushing SU1 4 3 5 TF c no 1 2 CP1 Contactor A2 A1 K1 GM c no 3 4 15 16 18 15 18 16 15 18 16 MV1 11 12 Solenoid valve Valve actuator SV1 13 15 14 3 2 1 NR1 A1 A2 B1 ...

Reviews: