Fläkt Woods
8217 GB 2014.07.02 15
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Advanced settings
Login
To enter the “Settings” menu for installers and service
personnel requires login.
The default passcode is
0000
. This can be changed
later.
Enter passcode
****
1. Enter the correct passcode and press the Confirm button.
For commissioning of fans, see following section
“Commissioning Wizard” on page 16.
For other settings, see Parameter list on pages 23–27.
Settings for installer and service personnel
1. Schedule
2. Run Commissioning Wizard
4. Fan Control
5. Heating / Cooling
3. Timer Control
Settings
6. Air Qualty
7. Alarm Configuration
9. Save Settings
10. Load Settings
8. Configure
Settings
11. Logout
Settings