AP BIO
Maintenance of the AP BIO
400/500/1000/2400
FG-DC_10523-GB_AP Bio_IOM-R0-12/2020 • Subject to modifications
27
9.2
Cleaning the air purifier
Observe current legal
regulations and standards!
FläktGroup recommends to
perform maintenance steps
and observe intervals
in conformity with
local regulations.
•
Use a dry cloth to remove dry coarse dirt.
•
Remove remaining dirt following a subsequent installation of add-on accessory
items.
•
For other contaminants use a dry cloth to remove dirt, if applicable wash off using
some water by adding alkaline cleaning agent.
•
For disinfectioning unit surfaces use cleaning agents specified in the following
sources: “List of disinfection procedures (DGHM)” issued by the German
Association for Hygiene and Microbiology, certificates issued by DVG and VAH
(German Association of Veterinary Medicine and the German Association for
Hygiene and Microbiology/Association for Applied Hygiene).
•
Refer to the above sources list for details and consider the specified concentration
and exposure time.
•
Use the following cleaning agents: e.g. BODE Microbak or DESOMED Desotop. For
correct concentration refer to the data sheet provided by the manufacturer and/or
select a non-visible small surface to test the solution there beforehand.
•
Using alcohol-containing agents is not allowed due to risk of explosion and fire.
•
Do not use abrasive sponges or tools that may scratch or scrape the protective
surface during cleaning (surface can be damaged).
•
Treat galvanized parts with a preservative spray.
•
Apply a lubricant spray to all moving parts, such as door latches and hinges
•
Clean gaskets on the doors and check for leaks, microbial growth and mould. It is
recommended to treat gaskets with a waterproof preservative.
Electrocution through hazardous voltage will lead to death or serious injury.
•
Disconnect the unit from the power supply and ensure the power cannot be
switched back on.
•
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover
or shield off neighboring live components.