eCO Premium™ - Installation & Maintenance
25
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
EXAMPLE 2 - WEEKLY SCHEDULE
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08:00 to 18:00 Monday to Thursday,
from 08:00 to 17:00 on Friday and 10:00 to 14:00 on Saturday. At
all other times, the fans are turned off.
If a post heater has been fitted, this will maintain the supply air
temperature at 20°C.
Day
Time
Fan Speed
Temp Setpoint
Monday
8-18
Normal
20° C
Tuesday
8-18
Normal
20° C
Wednesday
8-18
Normal
20° C
Thursday
8-18
Normal
20° C
Friday
8-17
Normal
20° C
Saturday
10-14
Normal
20° C
Other time
Stop
SCHEDULES (CONT)
EXAMPLE 3 - WEEKLY SCHEDULE
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08:00 to 18:00 Monday to Friday. At all
other times, the fans are configured to run at trickle speed. Note,
this schedule uses the higher priority of Weekly 2 schedule to
over-ride Weekly 1 schedule during the Monday to Friday normal
speed periods.
If a post heater has been fitted, this will maintain the supply air
temperature at 20°C from 08:00 to 18:00 Monday to Friday and at
18°C at all other times.
Day
Time
Fan Speed
Temp Setpoint
Monday
8-18
Normal
20° C
Tuesday
8-18
Normal
20° C
Wednesday
8-18
Normal
20° C
Thursday
8-18
Normal
20° C
Friday
8-18
Normal
20° C
Other time
Trickle (Low)
18° C