Commissioning
HyPower-Geko
106
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
Minimum heating limitation (variable):
Value can fall below the set minimum temperature value if the current room tempera-
ture value exceeds the setpoint by a value that is calculated as room temperature dif-
ference multiplied by effective factor.
– Advantage: Overheating of the room can be prevented or minimized by means of
the minimum limitation.
– Disadvantage: The supply-air temperature can fall below the minimum limitation
temperature value.
Factory setting and enter limits for effect factor:
– Default value1.0
– Minimum entered value0.4
– Maximum entered value4.0
Maximum heating temperature
If this function is activated and a temperature sensor is present in supply air, a tem-
perature value can be entered here. This value should not exceed the supply-air tem-
perature.
Factory setting and entered limit values:
– Default value60.0 °C
– Minimum entered value25.0 °C
– Maximum entered value60.0 °C
Minimum cooling temperature
If this function is activated and a temperature sensor is present in supply air, a tem-
perature value can be entered here. This value should not fall below the supply-air tem-
perature.
Factory setting and entered limit values:
– Default value10.0 °C
– Minimum entered value10.0 °C
– Maximum entered value20.0 °C