Maintenance and Troubleshooting
HyPower-Geko
122
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
Pos. 1:
Half-round hole at the
edge of the end piece
Pos. 2: Condensate tray
Pos. 3:
Plastic end piece
of the suction hose
of the condensate pump
•
Subsequently, check the proper operation of condensate drainage from the coil drip
tray and the on-site trap, if there is one.
8.3.6 Check fan
•
Dismount the drain pan as described in Chapter 8.3.5
•
Open the filter flap (see fig. 8-7, Pos. 3) as described in Chapter 8.2.1 and remove
the filter if necessary.
•
Disassemble the cover panel of the fan chamber (see fig. 8-7, Pos. 1, 2 screws
each right and left).
•
Check the fan(s) for ease of movement
(see fig. 8-7, Pos. 4).
•
Remove soiling within the casing with a vacuum cleaner.
Fig. 8-6:
Assembly of the plastic end piece of the suction hose of the condensate pump
User instructions!
Do not mount components in case of a subsequent check of fans!
Risk of personal injury!
Injury may be caused by falling parts and sharp edges!
Upon disassembly of the unit, wear helmet, safety shoes and protective gloves. Dis-
assembly should always be performed by two persons