HyPower-Geko
Maintenance and Troubleshooting
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
127
Pos. 1:
Sensor holder
Pos. 2:
Cable penetration
Pos. 3:
Nut of the cable sleeve
Pos. 4:
Cable with sensors
Pos. 5:
Seal - O-Ring
•
Lubricate the drain connection of the condensate tray including its O-ring (see fig. 8-
12, Pos. 7) with lubricant. Set the plastic end piece of the suction hose of the
condensate pump (seefig. 8-13, Pos. 3) on the intake fitting of the condensate tray
(seefig. 8-13, Pos. 2) until it sits firmly. For the assembly of the end piece of the
condensate pump, make sure that the half-round hole at the edge of the end piece
(see fig. 8-13, Pos. 1) is on the upper side.
Pos. 1:
Half-round hole at the
edge of the end piece
Pos. 2: Condensate tray
Pos. 3: Plastic end piece
of the suction hose
of the condensate pump
8.4.2 Checking condensate pump function
Only applicable to units with an integrated condensate pump.
Check the function of the condensate pump as described in Chapter 7.11.
Fig. 8-12: Clean the humidity sensor
Fig. 8-13: Assembly of the plastic end piece of the suction hose of the condensate pump