HyPower-Geko
Technical Description
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
19
2.5.4 Electrical data for fans
2.5.5 Electrical data of valve actuators
2.6
Condensate pump
In cooling units, condensate may form and is collected in the coil drip tray. If a slope
for condensate drainage is not fitted, a condensate pump must be installed. This pump
drains condensate into drainage pipework located higher upstream.
2.6.1 Function of condensate drain
A separate level sensor is installed on the side of the unit at the condensate tray other than
the condensate pump, which performs the following functions:
– Start of the condensate pump when the condensate level exceeds 4 mm from the
bottom of the condensate tray.
– Switch-off of the condensate pump after the condensate is pumped out.
– Sends the signal ALARM if the maximum permitted height of the condensate level
of 12 mm from the bottom of the condensate tray is exceeded.
Model size
Fan type
Current consumption [A]*
)
Power consumption [W]*
)
Min. / Max.
Min. / Max.
VK A
VK B
VK C
VK A
VK B
VK C
1
AC
0.64 / 0.98
0.57 / 0.75
0.56 / 0.69
131 / 224
118 / 172
116 / 157
2
0.93 / 1.90
0.87 / 1.30
0.85 / 1.15
180 / 431
174 / 293
171 / 254
3
0.94 / 2.15
0.89 / 1.76
0.92 / 1.74
194 / 490
186 / 405
185 / 396
4
1.97 / 3.09
1.86 / 2.46
1.84 / 2.39
415 / 708
381 / 555
376 / 540
1
EC
0.13 / 1.54
0.11 / 1.47
0.11 / 1.44
20 / 213
18 / 212
16 / 206
2
0.18 / 2.09
0.16 / 2.10
0.15 / 2.07
17 / 296
13 / 300
11 / 288
3
0.30 / 3.43
0.26 / 3.47
0.23 / 3.47
33 / 510
27 / 485
26 / 471
4
0.29 / 3.76
0.26 / 3.98
0.23 / 3.83
30 / 591
25 / 573
23 / 541
*) For control voltage 2-10V at 0 Pa external pressure (free intake and discharge)
VK .... Fan chamber
Tab. 2-16: Electrical data for fans 230 V, 50 Hz
2- and 3-way valves
on/off control mode
(thermoelectric actuator)
2- and 3-way valves
modulating operation
(modulating actuator)
2- and 3-way valves
continuous operation
(continuous actuator)
Starting current
[A]
Operating
current [A]
Power
consumption
[W]
Current
consumption
[A]
Power
consumption
[W]
Current
consumption
[A]
Power
consumption
[W]
230 V
24 V
230 V
24 V
230 V
24 V
230 V
24 V
230 V
24 V
24 V
24 V
0,6
0,7
0,013
0,09
3
3
0,03
0,03
7
0,7
0,06
1,4
Tab. 2-17: Electrical data of valve actuators at 230 V, 50 Hz and 24 V, 50 Hz (and 0-10 V signal)
User instructions!
For fusing, observe the values specified in the connection diagrams (see Unknown
source of cross-reference, Unknown source of cross-reference).