HyPower-Geko
Electrical connection
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
69
6.7.9 Connecting status and fault signal
6.7.10 Connecting function inputs and outputs
MATRIX
2001
3001
4001
4001+IO
9
9
9
It is possible to tap the status and alarm messages on the con-
trollers using floating contacts. The contact load at 230 V AC
amounts to a maximum of 4 A ohmic / 2 A inductive.
•
Connect in accordance with the wiring diagram.
Operation:
Contact closed on terminal 120 -121
Fault:
contact closed on terminal 124 - 125
Fig. 6-23: Connecting status and fault signal
Air treatmen
t un
it with
MATRI
X
3
000
Fault
O
per
ation
MATRIX
2001
3001
4001
4001+IO
9
9
9
Function input can be assigned with different functions depend-
ing on the supplied control equipment.
To activate the function the contact must be:
– closed for economy mode operation
– open for unit OFF with frost protection
be.
This function can be changed using the service tool
MATRIX.PDA or service software MATRIX.PC.
•
Connect in accordance with the wiring diagram.
The loop resistance may not exceed 500 W.
Fig. 6-24: Connecting function input
Function inputs
Functional inputs can be assigned with different functions:
– Normal operation
– Economy mode
– Autonomous operating mode (the functions of these operat-
ing modes can be programmed using the service software
MATRIX.PC)
– Switching the unit off (without frost-free condition in room)
Function outputs
The control contains 2 function outputs:
– Heating request (max. 250 V/5 A ohmic/2 A inductive)
– Cooling request (max. 250 V/5 A ohmic/2 A inductive)
If no jumpers are set at 100-230 and 100-232, outputs 230-231
and 232-233 can be used as volt free outputs (max. 2 A).
•
Connect in accordance with the wiring diagram.
The loop resistance may not exceed 500 W.
Fig. 6-25: Wiring function inputs and outputs
A
ir
treatm
e
nt
un
it w
ith
MA
TRIX 3000
Function input
as
floating contact
D30[230]
D31[231]
D00[100]
D32[232]
D33[233]
D00[100]
D2[62]
D3[63]
D4[64]
D5[65]
D6[66]
D7[67]
D8[68]
D9[69]
N
N
L
4A
A
ir t
re
a
tm
e
nt
un
it
wi
th
MATR
IX 4000 an
d IO-
add-
on
card
Cooling
Jumper on-site by
others
Heating
Autonomous
operating mode
Unit OFF
Economy mode
Normal
operation
Jumper on-site by
others
MATRIX
2001
3001
4001
4001+IO
9