23
OWNER’S MANUAL
NEUTON™
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
zone 4 enthalpy
zone enthalpy calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:437
DEV:2402
zone_4_enth_1
zone 4 grains
zone grains calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:438
DEV:2402
zone_4_grains_1
zone 5 dewpoint
zone dewpoint calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:539
DEV:2402
zone_5_dewpt_1
zone 5 enthalpy
zone enthalpy calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:540
DEV:2402
zone_5_enth_1
zone 5 grains
zone grains calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:541
DEV:2402
zone_5_grains_1
Zone RH 1
BAV
AV:711
DEV:2402
zone_rh_1_1
Zone RH 2
BAV
AV:712
DEV:2402
zone_rh_2_1
Zone RH 3
BAV
Zone RH 4
BAV
AV:714
DEV:2402
zone_rh_4_1
Zone RH 5
BAV
AV:715
DEV:2402
zone_rh_5_1
Zone Temp 1
BAV
AV:701
DEV:2402
zone_temp_1_1
Zone Temp 2
BAV
AV:702
DEV:2402
zone_temp_2_1
Zone Temp 3
BAV
AV:703
DEV:2402
zone_temp_3_1
Zone Temp 4
BAV
AV:704
DEV:2402
zone_tmp_4_1
Zone Temp 5
BAV
AV:705
DEV:2402
zone_tmp_5_1
allow co2
override
If this point is ON, and if the signal if
valid from the Zone Sensor CO2 sensor,
then if the space CO2 is greater than the
"CO2 force OCC mode setpoint", AV:3,
then occupied mode is forced .
BBV
BV:1
DEV:2402
allow_co2_
override_1
CO2 option
This point must be set to ON if CO2 is
included in the sensor
BBV
BV:2
DEV:2402
co2_opt_1
CO2 Override
Status
If CO2 option BV:2 is ON and conditions
are met, this status point will be on and
the mode will be Occupied .
BBV
BV:3
DEV:2402
co2_override_1
Cooling Mode
Status
Cooling Mode Status - if Heating Mode
has been off for 1 minute, and shutdown
mode is not active, and heat is called by
the thermostat, then Cooling Mode Status
is ON .
BBV
BV:5
DEV:2402
clg_status_1
Heating Mode
Status
Heating Mode Status - if Cooling Mode
has been off for 1 minute, and shutdown
mode is not active, and heat is called
by the thermostat, then Heating Mode
Status is ON .
BBV
BV:6
DEV:2402
htg_status_1
OCC command
from BAS
If this point is ON, the controller uses the
occupied setpoints
BBV
BV:7
DEV:2402
occupied_bas_1