Hydraulic Commissioning
1. Float Valve Setting
Ensure that the break tank float valve is set to its lowest position:
Pro PU Units
Pro PUm & Pro PDm Units
If a drain valve is fitted to the break tank, ensure that it is closed. Then, turn on the mains water supply and
allow the break tank to fill.
When the float valve operates for the first time, it may not close immediately, causing the break
tank to overfill. Once the internals of the valve have been fully wetted this should not occur again.
2. Bleeding Pumps
This step is only necessary for Pro PU / PUm / PDm units.
Make sure that the internal isolation valve within the pressurisation unit is closed. Failure to do
this may cause injury or damage to the equipment, system or property.