Program Parameter List
The table below gives details of all menu items, in the order that they will appear:
PR No
Customer Code - 2601
Notes
Default
Unit
0
Language
E=English I=Italian D=Deutsch F=French
N=Netherland
E
2
Low Pressure Alarm
0.5 bar less than Fill Pressure
0.5
Bar
STA
N
D
ARD
O
P
TION
3
Low Pressure Warning
0.6 Bar less than Fill Pressure
0.6
Bar
4
Differential
‘cut
-
in’ and ‘cut
-
out’
between pumps
0.2
Bar
5
Fill Pressure
System pr 0.3 venting
allowance
1
Bar
6
High Pressure Warning
High pressure alarm
–
0.1 Bar
2.6
Bar
7
High Pressure Alarm
System safety valve - 10%
2.7
Bar
8
Flood Limit
10
minutes
9
Excessive Start Quantity
0
10
Excessive Start Time
8
hours
28
Fill system
N
45
Service Reminder Y/N
N
48
ID Number
MODBUS ID number
1
49
Review Logs
N
50 (*)
Counter for P1 used for Topup
51 (*)
Hours Run for P1 Topup
52 (*)
Counter for P2 used for Topup
53 (*)
Hours Run for P2 Topup
54 (*)
Total Hours run P1 (inc Degassing)
55 (*)
Total Hours run P2 (inc Degassing)
56 (*)
Alarm Counter
57 (*)
Power interrupted counter
(*)
IF REVIEW LOG IS YES THEM PR NUMBER 50 - 57 WILL BE ACTIVE
This menu only brings up standard option for the pressurisation equipment, to set up the degasser option of the
equipment then you need to put in
4706
code and follow the menu list on the next pages.