© 2018 Flamco group. All rights reserved.
We reserve the right to change designs and technical specifications of our products.
Errors and omissions excepted.
Rev 1.0 Aug-18
Page
23
/
44
If the pump has a plastic bleed screw like the one shown below, do not use excessive force or
attempt to use any tools to turn it as this may damage the pump casing. Turn the plastic cap ¼
Anti-clockwise and lift the plug above the gap. Once water slip out push back cap by ¼ turn
clockwise.
3. Forcing Pumps to Run
Turn on the power supply to the digital controller and wait for the system pressure to appear on
the display. Then, enter the code 2601, Language menu will appear as default [E]. Press and hold
(MUTE) & (+) for pump 1 to run and Press and hold (MUTE) & (-) for pump 2 to run
Key:
(MUTE) & (+) = Pump 1 Run
(MUTE) & (-) = Pump 2 Run
To bleed the pumps, the pumps must be started. Then while the pump is running, the bleed screw
must be opened until all the air has been removed and only water is being discharged. The bleed
screw can then be closed.
Failure to bleed the pumps may result in damage to the equipment, system and property.
After bleeding the pumps, close the drain valve and remove the hose from the hose tail