FlameStop FDCIE Panels With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 3
Chapter 1 Product Overview
The panel is easy to install and operate and optional programming functions are enabled by
internal dip switches.
This series of panels are basically the same in application and operation, their only main
differences being the amount of zones and the size of the cabinets.
1.1 Features
Up to 16 zones can be detected, compatible with FlameStop conventional detectors and
manual call points.
Three sounder outputs, one alarm output, one fault output and one disable/supervisory
output.
Able to report short and open circuits of zones, sounder outputs and alarm output.
Test and disable functions
Programmable on manual call point connection, sound modes, sounder delay modes and
output delay modes.
Three access levels settable via the key switch and the internal switch.
Reserved repeater panel interface for fire alarm indication of multiple zones.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
1.2 Technical Specifications
1.2.1 Operating Voltage
Input Voltage: 220V/230VAC
+10%
-15%
Frequency:
50/60Hz
Input Current: 0.6 A
Fuse: 250VAC, T2A in SPS
Recommended Wiring: 1.5mm
2
or above of twin and earth cable, complying with local
installation codes. Please check your local requirements.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: An external load circuit breaker should always be installed for protection.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
1.2.2 Batteries
Minimum Operating Voltage: 21.5V
Maximum Charging Current: 320mA
Maximum Charging Voltage: 27.6V
Battery Type: Sealed lead-acid battery
Minimum Batteries: 2 batteries, 7Ah/12VDC
Recommended Battery and Model: AUSCELL CJ12-7