FlameStop FDCIE Panels With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 4
1.2.3 Detection Zone
Zone Voltage: 15VDC~28VDC
4.7k
Ω
End of Line Resistor
Resistance range for fire alarm using a clean contact is normally 470
Ω
Recommended Wiring: 1.0mm
2
or above 2 core cable, complying with local installation
codes.
Recommended Cable Length: not longer than 1000m
1.2.4 Output Interface
Fault Output
Type: normally open/close contact output
Contact capacity: 1A/24VDC
Disable/Supervisory Output (defaulted disable output)
Type: normally open/close contact output
Contact capacity: 1A/24VDC
Alarm output
Type: voltage contact output, normally open/close contact output are available,
(defaulted normally open contact output)
Contact capacity: 1A/24VDC
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor:
4.7k
Ω
Sounder output 1
Type: voltage contact output, normally open/close contact output (defaulted voltage
contact output)
Contact capacity: 1A/24VDC
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor:
4.7k
Ω
Sounder 2/3 output
Type: voltage contact output
Output voltage: 18VDC~28VDC
Output current: 300mA in alarm
End-of-line-resistor:
4.7k
Ω
Auxiliary Power Output
Output Voltage: 18VDC~28VDC
Output current: 450mA in standby mode and Maximum 1000mA in alarm mode when
the
Alarm Output
has been set to a normally open/close contact type. (Refer 3.2)