2.4 Zone Input Connection
Please refer to your local installation standards to ensure you are complying with the maximum
amount of devices which can be connected to any single zone. Also be sure to allow for all of the
devices in your battery calculations talked about in Chapter 5.
A 4.7k
Ω
resistor is required at the end of each detection zone, as shown in Fig. 2- 4 and Fig 2-5.
FlameStop PH-DZ03 Detector Base
4.7K
EOL
Fig 2-4
Remote Indicator Wiring for PH-DZ03 Base
+
+
+
+
-
-
OUT TO NEXT DEVICE
OUT TO NEXT DEVICE
OUT TO NEXT DEVICE
-
-