FlameStop FDCIE Panels With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 28
3.7 Setting Auxiliary Functions
RESOUND MODE: When the “6” of SW2 (
RESOUND MODE
) is set to the ON position,
resound mode is turned on. When there is fire alarm from a zone, the sounder outputs
associated to this zone will be started. Pressing
SILENCE/RESOUND ALARM
key and these
sounder outputs can be silenced; if there is an alarm signal from another zone at this moment,
the silenced sounder outputs that are not associated to this new alarm zone will resound. If
resound mode is turned off, the silenced sounder outputs not associated to this new alarm
zone will remain silenced. Default setting is ON.
SILENCE RESET MODE: When the “7” of SW2 (
SIL-RESET MODE
) is set to the ON position,
silence-reset mode is turned on. When there is fire alarm from a zone and its associated
sounder outputs are started, the FDCIE will not be reset until the sounder outputs are silenced.
If silence-reset mode is turned off, the FDCIE can be reset immediately. Default setting is ON.
SILENCE DELAY MODE: When the “8” of SW2 (
SIL-DEALY MODE
) is set to the ON position,
silence-delay mode is turned on. When there is fire alarm from a zone and its associated
sounder outputs are started, the FDCIE has to stay in fire condition for 3 minutes before the
sounder outputs could be silenced. If silence-delay mode is turned off, the sounder outputs
can be silenced immediately. Default setting is OFF.
TEST ZONE OUTPUT MODE: When the “5” of SW3 (
TEST ZONE OUT
) is set to the ON
position, test zone output mode is turned on. When a zone is in test mode and there is an
alarm signal, coming from the zone, the sounder outputs associated to the zone will be
automatically activated for 15 seconds. If test zone output mode is turned off, the sounder
outputs will not be activated. Default setting is OFF.
DISABLE/SUPERVISED OUTPUT MODE: When the “6” of SW3 (
DIS. / SUP. OUT
) is set to
the OFF position, the disable/supervised relay output is set for disable output; otherwise, this
output is set for supervised output. Default setting is OFF.
RELAY OUTPUT MODE: When the “7” of SW3 (
RELAY OUTPUT
) is set to the OFF position,
the FAULT1 to FAULT16 on relay board are defaulted as fault outputs. When the “7” of SW3
(
RELAY OUTPUT
) of is set to the ON position, FAULT1 to FAULT16 on relay board are set to
general fire trips, which all will activate on any zone fire alarm. Default setting is OFF.
3.8 Ground Fault Detection
Shorting X6 (
EARTH FAULT
) with a jumper, the FDCIE will be able to detect an earth fault.
3.9 Auxiliary Power Setting
Shorting “24V” and “AUX” of X3 with a jumper, the
AUX SUPPLY
output will be constant. If
shorting “AUX” and “LOOP” of X3, the
AUX SUPPLY
output will drop for about 10 seconds when
the FDCIE is reset.