FlameStop FDCIE Panels With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 23
3.5 Programming Output Modes
All output settings programming has to be done under Access Level III. So before programming
the Outputs, please first enter Access Level III according to the instructions in Section 3.1.3.
The FDCIE can be programmed through keypad for the functions below:
Setting a zone “With Manual Call Point”. If a zone is set “With Manual Call Point”, a fire alarm
from the zone will activate its associated sounder outputs and alarm output, regardless of
whether the zone is set with delayed output or not;
Associating a zone with sounder outputs. The output mode, sound pattern, and delay time of
the sounders associated to the zone can be set respectively.
Setting delay time for alarm output.
3.5.1 Setting Zone “With Manual Call Point”
If a zone is set “With Manual Call Point”, any fire alarm coming from that zone (either from a
detector or a manual call point), the FDCIE will immediately alarm and activate all sounders
associated to that zone and the alarm output regardless of any delay setting. Basic steps are
shown below.
1 Enter access level III.
2 Set the “2” of SW2 (
MCP ZONE
) on control board to ON position.
3 Pressing the
OUTPUT PROGRAM
button, the
OUTPUT PROGRAM
LED illuminates
steadily and the amber LED of zone 1 flashes to show zone 1 is to be selected for “With
Manual Call Point” setup. And DELAY MODE led flashes. The
FAULT
LED will indicate
according to the FDCIE fault condition. Other indicators, except for the above mentioned
LEDs, will be turned off.
4 Pressing the
SCROLL
button toggles between zones 1 to 16.
5 The amber
LED for zone 1 to 16 will flash when the zone is selected. Pressing the
ENTER
button can
choose whether or not to program the zone as “With Manual Call Point” and the
FDCIE will give 1 second sound indication. The amber zone LED illuminates steadily to
indicate the zone is NOT programmed as “With Manual Call Point”.
6 Pressing the
CANCEL
button exits the programming mode and the
OUTPUT PROGRAM
LED will be turned off.
7 Set the “2” of SW2 (
MCP ZONE
) to OFF position.
8 Exit access level III.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: If one of the outputs (sounder outputs or alarm output) is programmed with delay, then there
should be at least one zone set as “With Manual Call Point” to ensure the delay could be
overrode for immediate output.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆