PFS200-2
Intelligent FDCIE With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 37
Fig. 6-19
Enter a 3-digit zone number or
“*” (by pressing
DISABLE
) at the cursor position after letter
“Z”.
Enter a 3-digit device address or
“*” (by pressing
DISABLE
) at the cursor position after letter
“C”.
Enter a 2-digit device type or
“*” (by pressing
DISABLE
) at the cursor position after letter
“T”.
“
*
” represents any number (0~9)
Example 1, in order to disable device at address number 001 of Zone No.1, you need to input in
sequence the zone number 001, device number 001 and device type 03.
Example 2, in order to disable all alarm devices with type number 01
~
11 of Zone No.1, you
need to input in sequence the zone number 001, device address *** and device type **. Please
note that the asterisk mark
“*” is not allowed for the type number of action devices with type
number 12
~
65.
6.3.4.2 Enabling Devices
In the screen shown in Fig. 6-14, input number 2, you can enter device enable screen as shown
in Fig. 6-20. Same as disabling devices, you can also enable all devices of a zone, a single
device (single-device enable), all loop sounders, or enable a device by user code.
Fig. 6-20
6.3.4.3 Disabling/Enabling Al
arm Outputs
Entering number
“3” in the screen of Fig. 6-14 will enter the screen for disabling/enabling
sounder output, as shown in Fig. 6-21.
Fig. 6-21
*Enable Devices*
1 Each Zone Fully
2
Individual Points
3 All Loop Sounder
4 Use Devices Code
Disable
Z000 C000 T00 NoDefine
*Dis/En-able Outputs*
1.
Sounder Circuit