PFS200-2
Intelligent FDCIE With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 50
Chapter 8 Maintenance
The FDCIE shall only be repaired by specially trained technicians. Please disconnect the power
before servicing.
8.1 Replacing the Battery
Type of battery: Sealed lead-acid battery
Recommended period for replacing the battery: 2 years
(25
℃
)
Recommended manufacturer: AUSCELL
Disposal of used batteries: Please properly dispose the used batteries according to your local
rules and regulations.
NOTE:
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
8.2 Replacing the Fuses
Table 8-1
Location
Mark
Rated Value
Power filter F7.820.323
F1
2A Delay
Power board F7.820. 829b
F1, F2
5A
Loop interface board F7.820. 828
F1, F2, F3
2A