background image

PFS200-2 
Intelligent FDCIE With AS4428.3-2010 Fascia

            

 

 

Installation and Operation Manual

 

  

                                                  

      

 

 

 

 

Page 59  

Appendix 1  Internal Connection Diagram 

+

-

To Enclosure

 

① 

Main Board

 

② 

Switch Board

 

 LCD

 

④ 

Printer

 

⑤ 

 Buzzer

 

⑥ 

Loop Interface Board

 

⑦ 

Power Board

 

 Transformer

 

⑨ 

Power Filter

 

⑩ 

ZCP

 

⑪ 

Loop Board 

 

 

 
 
 
 
 
 
 
 

Summary of Contents for PFS200-2

Page 1: ...Issue 1 06...

Page 2: ......

Page 3: ...Display Area 9 3 1 2 Description of LEDs 9 3 1 3 Description of Buttons 10 3 1 4 Zone Indication and Manual Interventional Panel ZCP 11 3 2 Components 12 3 2 1 Standard Components 12 3 2 2 Optional U...

Page 4: ...g the panel 34 6 3 Instructions for Operator Operator Password Required 34 6 3 1 Resetting the system 34 6 3 2 Alarm Silence 35 6 3 3 Evacuation 35 6 3 4 Disable Enable 35 6 3 5 User Mode 38 6 3 6 Dev...

Page 5: ...tion Card For Programming 67 Appendix 8 How to Conduct a Test on the Addressable Panel 68 Appendix 9 Browsing Devices Connected to the Fire Panel 69 FlameStop Disclaimer All possible care has been tak...

Page 6: ...tion Consult with the appropriate authority having jurisdiction for confirmation of the requirements The PFS200 2 FDCIE shall only be installed and serviced by specially trained fire alarm system tech...

Page 7: ...ices 7 8 Outputs to fire protection equipment 7 10 The power supply of PFS200 2 FDCIE complies with AS 7240 4 requirements AC DC 100W Power Supply Functions AS 7240 4 Clause Power supply from the main...

Page 8: ...5 photoelectric smoke detector PHI 9102 complying with AS 7240 7 intelligent manual call point PXDI 9204 complying with AS 7240 11 intelligent reflective beam detector PHI 9105R complying with AS 724...

Page 9: ...scent Current under Full loaded Condition 0 75A Maximum Battery Operating Current 2 82A 2 3 Communication Loop Parameters 2 3 1 RS485 Communication Loop NETWORK A B Communication cable for connecting...

Page 10: ...d loop returning to the FDCIE Output Voltage 21V 27V pulse Output Current 0mA 300mA Type of Loop Class A loop Recommended Cable Length 1000m 2 5 Output Loop Parameters Recommended cable length 1000m 2...

Page 11: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 6 2 6 Dimensions 420mm 700mm 172mm...

Page 12: ...Page 7 Chapter 3 Construction and Components 3 1 Appearance and Internal Construction PFS200 2 FDCIE is flush mounted Its appearance and internal structure are shown in Fig 3 1 and 3 2 Fig 3 1 Clock L...

Page 13: ...With AS4428 3 2010 Fascia Installation and Operation Manual Page 8 Fig 3 2 Display control Zone indication board Printer Intelligent manual call point Buzzer Power supply Loop interface board Transfo...

Page 14: ...r battery or charger of the FDCIE is in fault condition It goes out when the fault is cleared POWER Green It illuminates when connected to mains power or battery SYSTEM FAULT Yellow It illuminates if...

Page 15: ...ng information on the current screen Also used for or the asterisk character For moving the cursor up or down EVAC For starting all sounders in the system and lighting the EVACUATE LED ENTER Confirmin...

Page 16: ...password ESC For canceling or exiting the operating menu If it s pressed when the FDCIE is displaying messages it will resume to display messages of the highest level 0 9 For entering numbers 3 1 4 Z...

Page 17: ...f main board loop interface board power supply display area and zone indication and manual intervention panel ZCP Main board Main board is the core of the FDCIE which contains CPU and interfaces to ot...

Page 18: ...board 3 Class A output wiring method is the same as that of Class A detection loop on loop interface board Refer to Section 4 4 3 4 for details 4 Loop shift indicator HL1 red It illuminates when the...

Page 19: ...ors mounted in the protected area transmit monitoring message to the FDCIE through Class A loop Every detector has its own address which the FDCIE can supervise the information of alarm fault and norm...

Page 20: ...uch as PXI 9403 can be connected to the loop of PFS200 2 After activation it will generate strong audible visual alarm signal 3 3 6 Repeater Panel PFS852RP Repeater Panel is designed with a microproce...

Page 21: ...tallation check the following items Check Engineering Requirement Check the components according to packing list The main items to be examined are installation and operation manual keys to the FDCIE e...

Page 22: ...2010 Fascia Installation and Operation Manual Page 17 4 2 Installing the Cabinet Mounting holes of the cabinet is shown in Fig 4 1 Ambient conditions for installation of the FDCIE Temperature 0 40 Rel...

Page 23: ...Power PFS200 2 FDCIE receives power from a 220V 230VAC 50Hz 60Hz supply The current flows through a filter to the transformer The transformer converts the input mains voltage to 27VAC The incoming po...

Page 24: ...Connection of Peripheral Devices Terminals of loop interface board are shown in Fig 4 3 Fig 4 3 Caution Do not connect power to your device until you have completed all input and output connections F...

Page 25: ...6 It outputs according to settings when there is isolation FIRE ALARM OUTPUT XT5 It outputs when there is fire alarm LOOP BUS XT2 XT4 Class A loop can connect with up to 235 addressable devices With l...

Page 26: ...R CIRCUIT OUTPUT is shown in Fig 4 4 Sounder Output Terminal Inside Panel Fig 4 4 A 4 7k resistor is connected at the SOUNDER CIRCUIT OUTPUT XT7 as factory default Connect the cable in correct polarit...

Page 27: ...een Rebooting the FDCIE by pressing SK1 button on rear of panel door will register the devices automatically Please check if the number of devices programming and operation state is in compliance with...

Page 28: ...f test and enter normal standby state The system will display as in Fig 5 1 if it is in normal state otherwise it will display abnormal information 5 1 Normal Information The normal display is shown i...

Page 29: ...rst fire alarm signal Last Fire Zone 003 Zone number of the last fire alarm Zone 3 Device 061 Description of zone with the last fire alarm and description of the device of that zone with the first fir...

Page 30: ...V or if there is charging fault the panel reports power fault and Light COMMON FAULT and POWER FAULT LED The LCD displays the type of the fault The panel generates fault sound Fault relay outputs Syst...

Page 31: ...he fault message The fault screen is as in Fig 5 5 in zone display mode and as in Fig 5 6 in loop display mode Fig 5 5 001 0f 002 FAULT10 18 There are two zones reporting fault and this is the first f...

Page 32: ...ules for Message Display If there are multiple messages in the system they will be displayed in the following order fire alarm fault action disable 1 The earliest fire alarm is displayed in priority T...

Page 33: ...ursor to modify any character Pressing TAB the highlight moves to the next position and returns to the first after the last position Wherever the cursor is Pressing ENTER button all the input data wil...

Page 34: ...than one piece of message on the LCD You can view details of this item by pressing ENTER or exit by pressing ESC When the printer is set as All History mode pressing ENTER while browsing can print th...

Page 35: ...e added total number of devices is 4 Zone 001 office1 Zone number and location NO 001 Optical Device address and type Sensitivity Nominal Device properties Office1 Device position Entering number 3 to...

Page 36: ...e 1 is in test mode Zone description is office1 Zone 05 office5 Zone 5 is in test mode Zone description is office5 Entering number 5 to choose 5 COM Devices will enter the screen for browsing network...

Page 37: ...ed If events with the same zone number and device type reach a defined number this special condition comes into effect Asterisk represents any number used in special conditions Event It is the message...

Page 38: ...screen is displaying non fault messages The display varies by the type of fault messages Please refer to Section 5 3 6 2 2 6 Browsing disable messages You can view disable messages by pressing VIEW DI...

Page 39: ...CE BUZZER can stop the sound of buzzer pressing SILENCE BUZZER again the FDCIE is still in mute state It will only sound by priority when new event appears 6 3 Instructions for Operator Operator Passw...

Page 40: ...he condition of a device cannot be removed immediately This device can then be temporarily disabled and re enabled after it s repaired The disabling enabling of delay can be set as needed For example...

Page 41: ...in Fig 6 17 Fig 6 17 Entering a 1 digit loop number 1 or 2 and 3 digit address number between 1 242 and then pressing ENTER will disable the selected device Disabling all loop sounders Entering number...

Page 42: ...f Zone No 1 you need to input in sequence the zone number 001 device address and device type Please note that the asterisk mark is not allowed for the type number of action devices with type number 12...

Page 43: ...et delay time and light DELAY MODE LED Note If the fire alarm is from a manual call point then the system will output immediately despite any delay settings 6 3 4 5 Deleting Disabled Information in Ne...

Page 44: ...enter the screen for setting up display mode as shown in Fig 6 26 Fig 6 26 In this screen choosing 1 Zone Mode can browse system messages by zone and choosing 2 Loop Mode can browse by loop 6 3 5 3 P...

Page 45: ...reased by PAS DELAY 0 180s setup After the delay of any stage expires the pre alarm will change to fire alarm and fire protection devices in the system will be started During any stage of delay if the...

Page 46: ...7 Test Mode Setup Pressing TEST can enter test mode setup screen as shown in Fig 6 31 Fig 6 31 In this screen the user can carry out self test on audible visual performance setting up single zone tes...

Page 47: ...enter the screen for exiting single zone test mode as shown in Fig 6 33 Fig 6 33 Entering the number of the zone to exit test mode and pressing ENTER to confirm will enable the zone to exit test mode...

Page 48: ...and press TAB then the next cell is highlighted Pressing ENTER will save the modification Fig 6 36 6 4 2 Modifying Password Entering 2 on the screen in Fig 6 35 the system enters the window for passwo...

Page 49: ...Fig 6 39 Entering the new password again if the two passwords are the same the LCD will display the window shown in Fig 6 40 meaning the modification is successful Fig 6 40 6 4 3 Network Setup Input...

Page 50: ...sing 4 on the screen shown in Fig 6 35 you can set beginning zone number of the FDCIE in network Duplicate zone number should be avoided The screen is shown in Fig 6 44 Entering the number of zones in...

Page 51: ...That is if any fire alarm comes If you have set the Delay Mode in Section 6 3 4 4 to Disable Sounder A and zonal sounder will be automatically started If you have set the Delay Mode in Section 6 3 4 4...

Page 52: ...n for resounding loop sounders as in Fig 6 48 Fig 6 48 6 4 5 3 1 Resounding Sounders of Other Zones Choosing 1 on the screen of Fig 6 48 the silenced sounders of all zones will be resounded on a new f...

Page 53: ...in alarm status and if it s between 0 120 the device is in fault 1 represents registration command and around 720 for normal status 2 represents the command for monitoring the commission status of PHI...

Page 54: ...ows C20 1 25 IQ x TQ FC IA x TA Where C20 battery capacity in Ah at 20 h discharge rate IQ total quiescent current TQ quiescent standby power source time normally 24 h FC capacity de rating factor IA...

Page 55: ...Sealed lead acid battery Recommended period for replacing the battery 2 years 25 Recommended manufacturer AUSCELL Disposal of used batteries Please properly dispose the used batteries according to you...

Page 56: ...s 4 Unable to register loop equipment Bus wrong or loose connection Check the loop 5 Unable to register repeater panels Wrong or loose connection of communication cables Check power supply to repeater...

Page 57: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 52 Chapter 9 Wiring Diagrams 9 1 Detector Base Wiring...

Page 58: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 53 9 2 PMI 9319 Zone Module Wiring...

Page 59: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 54 9 3 PMI 9300 Alarm Wiring...

Page 60: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 55 9 4 PMI 9300 Fault Wiring...

Page 61: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 56 9 5 Type E Detector into a PMI 9300...

Page 62: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 57 9 6 Addressable Duct Probe Detector...

Page 63: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 58 9 7 Beam Detector...

Page 64: ...AS4428 3 2010 Fascia Installation and Operation Manual Page 59 Appendix 1 Internal Connection Diagram To Enclosure Main Board Switch Board LCD Printer Buzzer Loop Interface Board Power Board Transfor...

Page 65: ...call point VAModule 12 Voice alarm module Sounder 13 Sounder strobe FTModule 14 Fire telephone module HR MCP 15 Hydrant pump HR Pump 16 Hydrant pump SPKR Pmp 17 Sprinkler pump PS SW 18 Stabilized pres...

Page 66: ...ly Unit EM Light 45 Emergency light EscapeLT 46 Escape light GasActiv 47 Gas activation Security 48 Security module ZoneValv 49 Zone valve Cylinder 50 Cylinder DelugePM 51 Deluge pump Undefine 52 Unde...

Page 67: ...ODE 1 LCD Contrast 2 Display Mode Zone Mode Loop Mode 3 Print Mode Disable Only Fire All History Pressing PRINT when viewing history records can print out the messages being viewed 4 PAS Positive Alar...

Page 68: ...ilencing all sounders in the system EVAC Start all sounder in the system for evacuation Operator Password Required LOCK Locking the keypad Turning pages ESC Canceling or exiting operation menu or enab...

Page 69: ...PFS200 2 Intelligent FDCIE With AS4428 3 2010 Fascia Installation and Operation Manual Page 64 Appendix 4 Thermal Detector Programming...

Page 70: ...nner door and press the SK1 button located on the back of the inner door Note Just tap this button quickly don t hold it down Refer to Connecting the Communication Card for Programming for SK1 locatio...

Page 71: ...cal Sum 005 says it is seeing 5 devices in total on the loop L1N001 Indicates Loop 1 and the Number of the Device All of the device numbers are displayed in consecutive order If you look at the exampl...

Page 72: ...nsure the ribbon cable is also connected to the second loop card before following any of the next steps 3 Follow all of the 7 steps on how to perform a Device Registration Note Be sure to press the RE...

Page 73: ...of Device whether it is a Type 02 R F Heat Detector or 03 Optical Detector If you don t know these details the next page walks you through how to Browse devices connected to the fire panel to help you...

Page 74: ...Browse Zone 002 Sum 039 L1N012 Optical L1N013 Optical L1N023 R F Heat L1N024 R F Heat L1N032 Optical Zone 2 has a Sum of 39 devices in total in this zone L1N001 Indicates Loop 1 Address 12 and Type 0...

Page 75: ......

Page 76: ...FlameStop Australia Pty Ltd Address 1 70 Gibbes Street Chatswood NSW 2067 Phone No 02 9932 2020 Fax No 02 9932 2022 Email Address sales flamestop com au Website www flamestop com au...

Reviews: