PFS200-2
Intelligent FDCIE With AS4428.3-2010 Fascia
Installation and Operation Manual
Page 3
Chapter 1 Product Introduction
PFS200-2 Intelligent FDCIE is designed to comply with AS4428.3-2010, AS7240.2 and
AS7240.4 standards with qualities of simple installation, operation, and easy maintenance. It is
used in fire alarm system with the following features:
It controls at most 30 zones. Each zone has its own alarm and fault/disable LEDs and a
label.
Maximum two Class A loops. The first loop can have up to 235 addressable devices, and
the second up to 242 devices. It is compatible with a series of addressable FlameStop
products, which are intelligent sounder strobe (PXI-9403) complying with AS 7240.3, rate of
rise and fixed temperature heat detector (PHI-9103) complying with AS 7240.5,
photoelectric smoke detector (PHI-9102) complying with AS 7240.7, intelligent manual call
point (PXDI-9204) complying with AS 7240.11, intelligent reflective beam detector
(PHI-9105R) complying with AS 7240.12, input and output module (PMI-9300, PMI-9301)
complying with EN 54-18, and loop isolator (PMC-9503) complying with EN 54-17.
The LCD can display 8 lines in total and 18 characters each line, assisting the 15 LEDs to
display important information.
The memory does not lose data even if power supply is accidentally removed.
It has manual buttons for each zone, which can activate/silence the sounder strobes
separately.
Automatically prompting operation steps for every alarm device and for smoke exhaust and
fire extinguishing equipment by field programming.
Sounder strobe interface provides 0.5A/24V output, compatible with FlameStop
conventional sounder strobe (PXC-9403) designed according to AS 7240.3.
RS232 interface enables communication with PC.
RS485 interface enables networking.