PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 10
Loop board
As the signal interface of the FACP, the loop board contains ports for detection
output that connects field devices and the FACP into a complete fire alarm system.
Power supply
It provides power to the main board, loop board and printer. Its backup feature
ensures that devices registered during commission will not be lost in case of power
fault.
Display and operation part
This part consists of switch board, keypad board, and LCD. It is used to indicate
and display different status of the system, and enables operations through keypad
(browsing, setting, printing and etc).
Zone indication panel
The zone indication panel can indicate fire alarm, fault/disable state of
corresponding devices.
3.2.2 Optional Components
SP-E32PK Printer
The printer is flush-mounted onto the front panel of the FACP. It can be simply
installed into the front panel by drilling a hole of fixed dimensions (103mm x 57mm).
The printer consists of front cover, rack, printing head, circuit board, scroll spindle
and printing paper. There are an
SEL
key and an
LF
key and an indicator on the
right top, and the exit with paper cutter. The printing head is installed inside the
frame, and the paper insert scoop is at its bottom. The printer is fixed onto the front
panel by the spring holders on the sides of the frame. The paper scroll is installed
on the frame with a flexible spindle. The whole printer together with the frame is
easily pulled out for paper replacement.
Network Card
PFSIFP8 provides two kinds of network cards: Local Network Card (RS485 card)
and Monitor & Control Card (RS232 card). The local network card has port I+/I- and
O+/O- for building up a ring or bus type network with other FlameStop FACPs. The
monitor & control card provides RS232 or USB port for communication with PC, so
that the FACP can connect with urban fire alarm and monitor network, or the central
monitor and control system in a building for integrated graphic control.
There is a decimal rotary switch on each loop board, communication board and
network board, for setting the channel number of the board. The loop board has
dual channels, and after the rotary switch set the number of the first channel, the
second channel will automatically get its number by adding one to the number of
the first. The numbers of the loop board, communication board and network board
can be mixed.
3.3 Periphery Devices
3.3.1 A Series of Intelligent Fire Detectors
Summary of Contents for PFSIFP8
Page 1: ......