PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 11
PFSIFP8 can connect with a series of fire detectors, such as PHI-9102, PHI-9103, and
PHI-9105R. The detectors mounted in the protected area transmit monitoring message
to the FACP through Class A loop. Every detector has its own address with which the
FACP can monitor the alarm, fault, and normal status of the detectors.
3.3.2 Modules
PFSIFP8 can connect to PMI-9300 Addressable Input Module & PMI-9301 Addressable
Single I/O Module. PMI-9300 module is used for receiving normally open digital signal
from fire protection device & transmitting the signal back to the fire alarm control panel.
PMI-9301 module is for connecting fire protection devices that need to be controlled by
the FACP, such as smoke valve, fresh air valve, and damper valve. It can also receive
answer signal from these devices.
3.3.3 Loop Isolator
Loop Isolator can remove the shorted part of loop from the whole system to ensure
normal operation of other devices and to ascertain the location of the part in fault. After
the fault is repaired, the loop isolator can automatically reset the removed part into the
system.
3.3.4 Manual Call Points
A series of manual call point (such as PXI-9202) can be connected to the loop of
PFSIFP8. When fire is confirmed manually, press the glass on the MCP, alarm signal
can be sent to the FACP. After receiving the alarm signal, the FACP will show the
number and location of the MCP, and sound alarm.
3.3.5 Sounder Strobes
Addressable
sounder strobe is a kind of audible/ visual alarm device installed in the
protected area, which can be activated by the FACP at the fire control center or by
manual call points. A series of FlameStop addressable sounder strobes (such as
PXI-9403) can be connected to the loop of PFSIFP8. After activated, it will generate
strong audible/ visual alarm signal.
3.3.6 Repeater Panel
PFS852RP Repeater Panel is designed with a microprocessor. When one or more
detectors alarm fire, the repeater panel can display the location and alarm message of
the detectors with audible and visual signals. Through communication loops, it can be
connected with FACPs, disposing and displaying the data from the FACPs. When
monitoring several floors or several zones with one fire alarm control panel, a repeater
panel on each floor or in each zone can replace zonal fire alarm control panel.
3.4 Defining Tool
The software is used for editing and downloading definition of device and C&E equation.
Before the system starts operation, you need to define the device and C&E using this
software on a computer, and then download them to the FACP.