PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 30
FAR:OK FPE:DIS Commission 20:44:30
*******************************************
*PANEL STATUS*
LOOP: 02
POINTS: 0000
CRT CARD: 00
NETWORK CARD: 00
Main power voltage:001V
Standby power voltage:29.6V
Main borad software version:V1.0
Fig. 6-7
6.2.1.6 Browsing Event and Command Equations
Choosing 6 on the screen shown in Fig. 6-2 will enter the screen for browsing the event
and command equations, as in Fig. 6-8.
FAR:OK FPE:DIS Commission 20:44:30
*******************************************
*BROWSE EVENT&COMMAND*
EVENT&COMMAND total num:001
No.001
110100302×10100302= 0000006499
0000006599 0000006699
Fig. 6-8
The part before “
=
” is the condition and that after it is the result.
“×” means “and”, and “
+
” means “or”.
A condition is composed of the following items:
101 001 02
Device type
Device address
Zone number of the device
Summary of Contents for PFSIFP8