PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 33
Fig. 6-12
Choosing “1. Disable” in the above screen, delay output of all output-type devices is not
allowed, and the FACP enters night mode compulsorily. If alarm dependency Type A or
Type B is set and the condition for dependency is not met within the pre-alarm delay
period, the pre-alarm will be automatically cancelled.
Choosing “2. Enable”, delay output of all output-type devices is allowed, and the FACP
enters day mode or night mode according to the pre-set start/stop time. If, when the
FACP works in day mode, alarm dependency Type A or Type B is set and the condition
for dependency is not met within the pre-alarm delay period, the pre-alarm will
automatically change to fire alarm.
6.2.5 Fire Alarm Acknowledgement Timer
Choosing 5 on the screen shown in Fig. 6-1 will enter the screen for setting up the time
for Stage 1 and Stage 2 of acknowledgement timer, as in Fig. 6-13.
FAR:OK FPE:DIS Commission 20:44:30
*******************************************
*ACKNOWLEDGE TIMER*
Please input the Pre-Alarm ACK time
Stage1 (Default 30S):[00]M-[30]S
Please input the Pre-Alarm verify time
Stage2 (Default 2M):[02]M-[00]S
Fig. 6-13
Summary of Contents for PFSIFP8