PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Chapter 1 Product Introduction
PFSIFP8 Intelligent Fire Alarm Control Panel (FACP) is designed to comply with
AS 7240.2 standard with qualities of simple installation, operation, and easy
maintenance. The fire alarm system has the following features:
It controls at most 140 zones, each of which has its own alarm and fault/disable
LEDs and a label. Every zone can be programmed to associate with fire alarm and
fire suppression devices.
Maximum 8 Class A loops, each with up to 242
addressable devices. It is compatible
with a series of addressable FlameStop products, which are intelligent sounder
strobe (PXI-9403) complying with AS 7240.3, rate of rise and fixed temperature heat
detector (PHI-9103) complying with AS 7240.5,
photoelectric smoke detector
(PHI-9102) complying with AS 7240.7, intelligent manual call point (PXI-9202)
complying with AS 7240.11, intelligent reflective beam detector (PHI-9105R)
complying with AS 7240.12, input and output module (PMI-9300, PMI-9301)
complying with EN54-18, and loop isolator (PMC-9503) complying with EN54-17.
The LCD can display 15 lines in total and 40 characters each line, assisting the 17
LEDs to display important information.
The memory does not lose data even if power supply is accidentally removed.
Automatically prompting operation steps for every alarm device and for smoke
exhaust and fire extinguisher by field programming.
Sounder strobe interface provides
0.2A/24V
output, compatible with FlameStop
conventional sounder strobe (PXC-9403) designed according to AS 7240.3.
RS232/USB interface enables communication with PC.
RS485 interface enables networking.