PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 4
Chapter 2 Technical Specifications
2.1 Operating Voltage
Voltage:
220VAC/230VAC
+10%
-15%
Frequency:
50Hz/60Hz
Current:
1A
Recommended Wiring: 1.5mm
2
or above screened cable, complying with local
installation code.
2.2 Standby Batteries
Maximum Charge Current: 2A
±
0.1A
Maximum Charge Voltage: 27.3V
±
0.3V
Type: Sealed lead acid batteries
Maximum Charge Capacity: Two 12V/38Ah batteries
Recommended manufacturer and model of battery: Yuasa NP38-12I
Recommended Wiring (subject to local installation codes):
FireCable ® 2E/1.5 2 core and Earth 1.5mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1.5mm
2
CSA
2.3 Communication Loop Parameters
2.3.1 RS485 Communication Loop
NETWORK (I+, I-, O+, O-): Communication cable for connecting with up to 32
network FACPs.
Recommended Wiring (subject to local installation codes):
FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended Cable Length
≤
1000m
2.3.2 RS232 Communication Loop
Connecting with a PC for running graphic monitor system through a DB9 port or
USB port.
Connecting with PFS852RP Repeater Panel through REPEATER (A, B) port.
Recommended Wiring:
RS232: Standard RS-232 interface. The 2
nd
pin (for sending data), the 3
rd
pin
(for receiving data), and the 5
th
pin (ground) are connected with PC through
three-core screened cable
(Note: the length of cable should be less than
15m; the screening layer and computer’s enclosure should be earthed).
USB: Standard USB printer cable. The length of cable should be less than 3m.
REPEATER Port:
Recommended Wiring (subject to local installation codes):
FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended Cable Length
≤
1000m