PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 5
2.4 Detection Loop Parameters
LOOP OUT (O+, O-): Polarized signal cable from the FACP connecting up to 242
addressable devices.
LOOP IN (I+, I-): Polarized signal cable returning to the FACP.
Output Voltage: 21V~27V pulse
Output Current: 0mA~300mA
Type of Loop: Class A loop
Recommended Wiring (subject to local installation codes):
FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended Cable Length
≤
1000m
2.5 Output Loop Parameters
Recommended Wiring (subject to local installation codes):
FireCable ® 2E/1.0 2 core and Earth 1mm
2
CSA
Pirelli Cable Limited FP200 FLEX 2 core and Earth 1mm
2
CSA
Recommended cable length
≤
1000m
2.5.1 ALARM ROUTING (+, -)
Output Voltage: 21VDC ~27VDC
Output Current: 0mA~200mA
End of Line Resistor: 4.7k
Ω
2.5.2 FEED BACK (F1, F2)
End of Line Resistor: 4.7k
Ω
2.5.3 OUTPUT TO F.P.E. (+, -)
Output Voltage: 21VDC~27VDC
Output Current: 0mA~200mA
End of Line Resistor: 4.7k
Ω
2.5.4 OUTPUT TO SOUNDER (+, -)
Output Voltage: 21VDC~27VDC
Output Current: 0mA~1000mA
End of Line Resistor: 4.7k
Ω
2.5.5 FAULT OUTPUT (NC, COM, NO)
Contact Capacity: 24VDC @1.0A
In fault state, NC and COM open, NO and COM close.
2.6 Dimensions
484mm×191mm×850mm