VESDA-E VEP-A00-P Product Guide
18
www.xtralis.com
4.2
Mounting
The VEP-A00 detector can be mounted in an upright or inverted position. Do not mount the detector with a
sideways orientation as shown in Figure 4-3 below.
Figure 4-3: Sideways orientation
Ensure the mounting surface is flat as this allows an air tight seal to be achieved between the sampling pipe
and the tapered air inlet pipes on the detector.
Ensure that there is sufficient clearance to mount the detector (Figure 4-4), noting the location of air sampling
pipes and cable entry points. Due to the rigid nature of the plastic pipe, installation must provide for sufficient
movement in all pipework (air inlet, air exhaust and cable pipes) to allow pipe ends to be easily fitted and
removed.
A
B
Legend
A
Min. 50 mm (2 in.) below ceiling
level
B
Mounting Bracket:
The detector can be mounted
directly against a wall or
obstruction.
Refer to Section 4.2.2 for
further information.
Direct mounting:
A minimum clearance of 20 mm
(0.8 in.) is required between the
detector and a wall or
obstruction, on both sides of the
detector.
Refer to Section 4.2.3 for
further information.
Figure 4-4: Mounting location
Summary of Contents for VESDA-E VEP-A00-1P
Page 2: ......
Page 10: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEP A00 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEP A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A00 P Product Guide 106 www xtralis com Z zone 56 58 77 101 ...