VESDA-E VEP-A00-P Product Guide
34
www.xtralis.com
4.3.2
Socket Locations
SH
SH
NC C NO
NC C NO
NC C NO
2 [MINOR F]
NC C NO
1 [ISOL]
5 [ACTION]
NO C NC
6 - FIRE 1
NO C NC
7 [FIRE 2]
NO C NC
A
B
C
D
H
G
F
E
I
J
K
L
M
O
N
4 [ALERT]
3 - URGENT F
P
Legend
Power
A
Power Out
B
Power In
VESDAnet
C
VESDAnet B
D
VESDAnet A
Relays
E
1 - Disable (Isolate)
F
2 - Minor Fault
G
3 - Urgent Fault
H
4 - Alert
I
5 - Action
J
6 - Fire 1
K
7 - Fire 2
Comms
L
USB
M
Ethernet
GPI
N
Monitored GPI
O
Unmonitored GPI
Ground
P
Ground Reference
Terminal
Figure 4-33: Socket Locations
4.3.3
Power Source
There are two sets of power terminals on the main board (Figure 4-33). Connect a 24 VDC power supply which
is compliant with local fire protection codes and standards to the PWR IN socket, and if required loop out to
another detector via the PWR OUT socket.
The detector will not operate if the power supply polarity is reversed.
Caution:
Operating the detector when DC supply voltage is outside the specified voltage range may
cause damage to internal components. For further information refer to the Product
Specifications on page 9.
Attention :
Le détecteur de fonctionnement lorsque la tension d'alimentation DC est en dehors de la plage
de tension spécifiée peut endommager les composants internes. Pour plus d'informations, se
reporter au notice descriptive du produit à la page 9.
Summary of Contents for VESDA-E VEP-A00-1P
Page 2: ......
Page 10: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEP A00 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEP A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A00 P Product Guide 106 www xtralis com Z zone 56 58 77 101 ...