VESDA-E VEU-A10 Product Guide
www.xtralis.com
97
8
Troubleshooting
If the VEU-A10 detector identifies a fault condition, the Fault LED on the front of the detector illuminates and
an event containing details of the condition is written to the Xtralis VSC active event list and the detector's
event log. The buzzer will beep once every 30 seconds if the Urgent fault beep and Minor fault beep
checkboxes on the Relay configuration screen (section 5.5.10) are ticked.
The Xtralis VSC software can be used to obtain specific information on the event to enable further
investigation and correction of the fault. The Xtralis VSC Online Help contains descriptions of each fault and
recommended corrective actions.
8.1
Fault Reporting through Relays
VESDA-E devices are often interfaced with Fire Alarm Control Panels (FACPs) or building management
systems (BMS) via relays. In such instances the fault relays signal a fault condition to the FACP or the BMS.
Use the Xtralis VSC software to further investigate the fault.
8.2
Troubleshooting with the Front Panel Display
The main screen of the VESDA-E VEU-A10 touchscreen display features a range of fault indicators. When a
fault is generated, the respective indicator will illuminate. Use Xtralis VSC to further investigate the fault by
reviewing the event log.
Fault Indicator
Description
General detector fault, for example an electronics hardware fault, or fault
test procedure in progress.
Refer to Section 5.4 on page 58 for further information on the fault test
procedure.
Airflow fault, for example Airflow not within the expected range.
Power fault, for example Mains Power failure.
Communications fault, for example disconnected wiring on VESDAnet.
Aspirator fault, for example the aspirator impeller cannot rotate due to
contamination or the aspirator has an electrical fault.
Filter fault, for example the filter is not inserted, or requires replacement.
Smoke detection fault, for example a Smoke Sensor or Sampling Module
hardware failure. This indicator will also be lit when the Autolearn Smoke
function is canceled due to an alarm occurring during the Autolearn
process.
Table 8-1: Fault Indicators
Summary of Contents for VESDA-E VEU-A10
Page 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Page 2: ......
Page 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...