Mounting
The VEU-A10 detector can be mounted in an upright or inverted position. Do not mount the detector with a
sideways orientation as shown in Figure 4-3 below.
Figure 4-3: Sideways orientation
Ensure the mounting surface is flat as this allows an air tight seal to be achieved between the sampling pipe
and the tapered air inlet pipes on the detector.
Ensure that there is sufficient clearance to mount the detector (Figure 4-4), noting the location of air sampling
pipes and cable entry points. Due to the rigid nature of the plastic pipe, installation must provide for sufficient
movement in all pipework (air inlet, air exhaust and cable pipes) to allow pipe ends to be easily fitted and
removed.
A
B
Legend
A
Min. 50 mm (2 in.) below ceiling
level
B
Mounting Bracket:
The detector can be mounted
directly against a wall or
obstruction.
Refer to Section 4.2.2 for
further information.
Direct mounting:
A minimum clearance of 20 mm
(0.8 in.) is required between the
detector and a wall or
obstruction, on both sides of the
detector.
Refer to Section 4.2.3 for
further information.
Figure 4-4: Mounting location
Summary of Contents for VESDA-E VEU-A10
Page 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Page 2: ......
Page 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...