62 |
P a g e
11.
Minimum clearance directly above the fireplace inside the chase
–
non-combustible
–
All non-combustible studs to be
installed a minimum of ½” away from the fireplace. Metal studs should not connect to the fireplace or touch the fireplace.
Doing so will result in heat transfer from the fireplace to the metal stud. Make sure not to block hot air flow to the heat
release.
12.
Minimum clearance directly above the fireplace inside the chase
–
Combustible
•
First
18”
directly above the fireplace
MUST
be framed using non-combustible material. Metal Studs.
Zone A
•
All combustibles above the 18” must be covered.
Zone B.
There should be no combustible materials left uncovered above the fireplace inside the chase.
Fireplace chase should be designed and built to allow hot air to release from the unit and rise-up in a non-combustible
channel to the heat release.
13.
Chase celling-
Top of the chase must be covered with noncombustible material (Firestop). No exposed combustible
materials are allowed inside the chase.