49
|
Page
When using the power vent system, direction of flow through the vents can be up, down, horizontal or diagonal since the system
is sealed and vacuumed. The vent restrictor level should be set based on length in feet, number of elbows and the vent
termination.
NOTE:
A minimum of
20 feet of venting
is required between
the fireplace and the in-line power vent.
Do not use the power vent
if the vent routing is less than 20 feet.
Refer to the
Flare Power Vent Installation Manual
for more specific instructions
.
Clearance -
Clearances between the vent pipe and combustib
le materials must be maintained at 3” inches top and 1” for side
and below. Maintain the same clearance from the power vent box to any combustible materials.
Power vent unit must be installed by a qualified installer in accordance with these instructions.
CAUTION! Failure to install, operate, and maintain the power venting system in accordance with manufacturer's instructions
will result in conditions which may produce bodily injury and/or property damage