37
2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER, IT IS POSSIBLE TO SET THE
OPERATION TIME OF THE PUMP AFTER THE MAIN BURNER
TURNS OFF DUE TO THE ENVIRONMENT THERMOSTAT.
0 - 90
VALUE EXPRESSED IN
MULTIPLES OF 5 SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P09
POST-CIRCULATION DOMESTIC / STORAGE TIMING
THROUGH THIS PARAMETER, IT IS POSSIBLE TO SET THE
OPERATION TIME OF THE PUMP AFTER CLOSING THE TAP OR
REACHING THE TEMPERATURE SET IN THE BOILER.
0 - 90
VALUE EXPRESSED IN
MULTIPLES OF 5 SECONDS
(PRE-SET AT 24 X 5 = 120
SECONDS)
P10
DOMESTIC FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
SEE CHAPTER
‘
H
E
A
T
C A P A C I T Y
D I A G R A M
(KW) –
ELECTRIC FAN
F R E Q U E N C Y
(HZ)’
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P11
DOMESTIC FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
SEE CHAPTER
‘
H
E
A
T
C A P A C I T Y
D I A G R A M
(KW) –
ELECTRIC FAN
F R E Q U E N C Y
(HZ)’
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P12
HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
SEE CHAPTER
‘
H
E
A
T
C A P A C I T Y
D I A G R A M
(KW) –
ELECTRIC FAN
F R E Q U E N C Y
(HZ)’
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)