40
2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P17
DISABLEMENT OF DOMESTIC HOT WATER LINE BY MEANS OF
SWITCH (ONLY FOR FAST BOILERS)
(SEE EXCLUSION VIA CONTACT (TP) IN THE CHAPTER “OPTIONAL
ELECTRICAL CONNECTIONS”)
BY ENABLING THIS PARAMETER IN THE PRESENCE OF
A CONNECTION (FOR EXAMPLE A BOILER CLOCK OR A
TEMPERATURE THERMOSTAT) ON BOILER CLOCK SWITCH ON
THE BOARD, THE REQUEST FOR BURNER IGNITION ON THE
DOMESTIC HOT WATER LINE WILL BE DISABLED UPON BOILER
CLOCK SWITCH CLOSURE.
EXAMPLE 1:
WITH THE BOILER CLOCK SWITCH OPEN, UPON
THE REQUEST FOR DOMESTIC HOT WATER, THE FLOW SWITCH
AND THE BOILER WILL TURN ON.
EXAMPLE 2:
WITH THE BOILER CLOCK SWITCH CLOSE, UPON
THE REQUEST FOR DOMESTIC HOT WATER, THE FLOW SWITCH
AND THE BOILER WILL NOT TURN ON.
0 - 1
0 = DISABLED
(SET BY DEFAULT)
1 = ENABLED
P18
ENABLING BUS INDUSTRIAL PILOTING 0 -10V
THROUGH THIS PARAMETER YOU CAN ENABLE OR DISABLE THE
BUS INDUSTRIAL INPUT 0-10 V TO SET THROUGH EXTERNAL
BUS THE BURNER POWER OR THE DELIVERY TEMPERATURE.
0 - 2
0 = DISABLED
(SET BY DEFAULT)
1 = TEMPERATURE CONTROL
MODE
2 = POWER CONTROL MODE
P19
MINIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MINIMUM HEATING TEMPERATURE.
20 - 40
THE VALUE IS EXPRESSED IN °C
P20
MAXIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MAXIMUM HEATING TEMPERATURE.
40 - 90
THE VALUE IS EXPRESSED IN °C
P21
MAXIMUM DOMESTIC SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MAXIMUM DOMESTIC TEMPERATURE.
45 - 75
THE VALUE IS EXPRESSED IN °C
P22
SET POINT
'
T DELIVERY-RETURN
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE TEMPERATURE
DIFFERENCE BETWEEN DELIVERY AND RETURN.
0
0 = DISABLED
10 - 40
THE VALUE IS EXPRESSED IN °C