input of the cut-off flow for negative measured values
range: -12.7...0 cm/s
default: -2.5 cm/s
This display will only be indicated if
Cut-off Flow
=
sign
and
Cut-off
Flow
=
user
is selected.
x
input of the cut-off flow for the absolute value of the measured values
range: 0…12.7 cm/s
default: 2.5 cm/s
This display will only be indicated if
Cut-off Flow
=
absolut
and
Cut-
off Flow
=
user
is selected.
x
input of the max. signal amplification
range: 0...255
0: no limit of the signal amplification
This display will only be indicated if the SuperUser mode is activated.
x
input of the fixed upper limit of the sound speed
range: 0...3 000 m/s
0: the default limit of 1 848 m/s will be used
This display will only be indicated if the SuperUser mode is activated.
x
Input of the offset.
range: 0...900 m/s
0: the default limit of 300 m/s will be used
This display will only be indicated if the SuperUser mode is activated.
x
activation of the totalizers overflow
x
activation of the taking-over of the totalizer values after the measurement re-
start
x
input of a time interval after which the transmitter has to detect a long mea-
surement failure if there are no valid measured values
0: the default value of 30 s is used
This display will only be indicated if the SuperUser mode is activated.
x
input of the number of decimal places of the totalizers
Automatic
: dynamic adjustment
Fixed to x digit
: 0...4 decimal places
This display will only be indicated if the SuperUser mode is activated.
x
activation of the manual reset of the totalizers
This display will only be indicated if the SuperUser mode is activated.
x
activation of the display of the totalizer sum
This display will only be indicated if the SuperUser mode is activated.
x
activation of the display of the last valid measured value
This display will only be indicated if the SuperUser mode is activated.
x
activation of the turbulence mode
x
INIT-resis-
tant
-Cut-off Flow
-2.5
cm/s
Cut-off Flow
2.5
cm/s
A: Gain threshold
Fail if>
90
A: Bad soundspeed
thresh. 2007 m/s
A: Bad soundspeed
offset: +321
Quant. wrapping
off
>ON<
Quantity recall
off
>ON<
Do not total. if
no meas.>
0 s
Total digits
↕
Automatic
3xC clear totals
off
>ON<
Show
Σ
Q
off
>ON<
Keep display val
off
>ON<
Turbulence mode
off