21
K 2 . 1
9.2. ADJUSTMENT WITH CI600
CAUTION!
The unit's air supply
MUST be adjusted before the
unit is used for the first time. This
should be done in accordance with
the projection documents. Adjust
the values based on the projected
values.
i
9.2.1. Adjustment
Only stage 2 (NORMAL) needs to be adjusted.
Note that it is also possible to adjusted stages 1 and 3
with a CI600 control panel. This should only be done
if a special need arises, however. This is because it is
H[WUHPHO\LPSRUWDQWWRKDYHDGHTXDWHDLUȵRZUDWHV
7KHIXQFWLRQRIWKHGLHUHQWVWDJHV
MIN
Must not be used when the home is in use.
0XVWQRWEHXVHGLQWKHȴUVWWZRKHDWLQJ
seasons.
NORMAL
Used under normal conditions. On this setting
the air supply must be adjusted according to
current regulations.
MAX
Used if there is a need for increased air supply
on account of higher occupancy or a raised
humidity level, for example during showering
or when clothes are being dried. This setting is
normally used for limited periods.
First go to the ”Advanced user” menu, enter the PIN and
press OK:
PIN CODE
OK?
1 0 0 0
Then go to the ”Fan control” menu. The fans are
VHOHFWHGDQGFRQȴJXUHGLQWKLVPHQXVFUHHQ7KHQJRWR
adjustment of the extract air fan and supply air fan.
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
>
>
>
OK?
This dialog is identical for the supply air and extract air
fans. The fans are adjusted individually to the desired
capacity for the respective speed.
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
OK?
50%
75%
100%
Factory settings for supply air/extract air:
MIN
ȴ[HG
NORMAL
75% (variable)
MAX
ȴ[HG
9.2.2. Temperature regulation
In this menu screen (located under ”Advanced user”)
\RXFRQȴJXUHWKHWHPSHUDWXUHUHJXODWLRQDQGFRROLQJ
functions.
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
>
>
OK?
>