22
K 2 . 1
Regulation type
If supply air regulation is selected, no further settings
can be set here. If extract air regulation is selected,
the max. and min. supply air temperatures can also be
VSHFLȴHG
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
EXTR OK?
35°
15°
10. Adjusting the kitchen hood
If basic ventilation is desired via the kitchen hood, the
damper from the factory must be replaced. Replace
it with a damper with adjustment options. This is not
supplied with the unit.
10.1. FORCED VENTILATION
The unit has 4 forced ventilation options:
1. (Switch on front of unit.) This gives a half-open
damper which will increase the air volume passing
through the hood.
2. Turn the knob to position 2. This gives a fully open
damper which will allow even more air through the
kitchen hood.
3. Turn the knob to position 3. This will give a fully-open
damper which will allow even more air through the
kitchen hood, in that the fans go to speed 3.
4. The air volume through the unit can also be increased
by setting the fans to speed 3 via the control panel
(external panel). See separate instructions.
The damper needs closing again manually. There is no
timer in the damper. Closed in position O.
The air entering the unit through the kitchen hood does
not pass through the rotary heat exchanger (by-pass).