8
4 electrical Works
All electrical works must be performed by an authorised electrician.
• See the separate instructions for the automatic control and its installation.
• See the separate wiring diagram in the unit for external connections.
• See also Chapter 9 technical Data for more information on electrical wiring.
• A service switch must be installed for all-pole breaking of the supply voltage to the unit. this is not included
in the supply from FlexIt.
• the electrical components must not be exposed to temperatures lower than -23
0
C
or higher than +55
0
C
.
4.1 Main Supply (Mains Cable)
For the L50, 3 supply cables are required, 1 for the automatic control and 2 for the electric battery (there are 2 electrical
groups). Only 1 supply cable is required for the other units.
See the separate table in Chapter 9 Technical Data for the exact dimensions of each unit.
4.2 Connection of external Components
See the separate wiring diagram enclosed with each unit. All electrical connections must be installed by qualified
electricians.
4.3 earth-leakage Circuit-breaker
The frequency converter must be earthed to comply with the regulations concerning high leakage
currents (over 3.5 mA). If a line-side earth-leakage circuit-breaker is used as protection in accordance
with the installation regulations, an earth-leakage circuit-breaker type B must be installed, which
functions even if there are DC components. See the symbol in Fig. 9.
tighten all terminal blocks before finishing the work to avoid heat generation in the contacts, which
may result in fire in the worst case scenario.
Fig. 9 Earth-leakage
symbol
!
Summary of Contents for L12 X
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...Flexit AS Televeien 15 N 1870 Ørje www flexit com ...