15
8 CI600 advanced user menu
NB!
For more information on the ”Advanced
User” menu, refer to the ”CI600 Reference
Manual” on Flexit’s homepage.
8.1 PIN
To access the menu item, you need to enter the PIN 1 0 0 0.
PIN CODE
OK?
1 0 0 0
8.2 Advanced
user
This menu contains functions for monitoring, configuration
and troubleshooting. Information to do with adjustment
can be found in the installation instructions. Complete
documentation of all menus, including configuration for
accessories and extras, etc., is described in the CI600
reference manual, which is available at www.flexit.no.
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
>
OK?
>
>
>
>
8.3 Temperature
regulation
In this menu screen, you configure the temperature
regulation and cooling functions.
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
>
>
OK?
>
Regulation type
If supply air regulation is selected, no further settings can
be set here. If extract air regulation is selected, the max. and
min. supply air temperatures can also be specified.
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
EXTR OK?
35°
15°
Cooling
NB!
Flexit does not supply or project cooling
machines.
In this dialog, the cooling function is activated and the
parameters MIN OUTDOOR AIR TEMP for supply of cooling
and MIN SPEED for supply of cooling are specified. If a DX
cooling machine is used, the supply delay interval can be
specified.
COOLING
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
OK?
>
AV
18°
MIN
180 s
It is also possible to activate a function to recover cooling
in the building using the rotating heat exchanger. Enter
the desired difference between the outdoor and indoor air
temperatures for when the function is activated.
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
OFF
1°
OK?