FT-112(D) Panel Weighing Indicator, Technical Manual, Rev.1.0.0, May 2019
Page
64
of
170
[ 514 ZEROING
: 50%
] M Zeroing range with key.
Page 33
NO
2%
3%
20%
50%
:
:
:
:
:
Disable.
± 2%
± 3%
± 20%
± 50%
[ 515 AZTRACK
: 0.5d
] M Automatic zero tracking.
Page 33
NO
0.3d
0.5d
1d
2d
3d
:
:
:
:
:
:
Disable.
± 0,3d
± 0,5d
± 1d
± 2d
± 3d
[ 516 STABLE
: 0.5d
] M Stability detection range.
NO
0.3d
0.5d
1d
2d
3d
4d
:
:
:
:
:
:
:
Disable.
± 0,3d
± 0,5d
± 1d
± 2d
± 3d
± 4d
[ 517 STBTIME
: 0.7
]
Stability time.
The scale is accepted as a stable to process, If the scale is stable
during this time.
0.1…. 9.9 seconds.
[ 518 MIN TARE
: 20
]
Minimum tare for automatic taring
Taring can be done if loading is heavier than MIN TARE.
[ 519 MINWEIGT
: 20
]
Minimum weight to produce printout
The printout is produced if the load is heavier than MIN WEIGHT.
[ 51A TILT
: NO
] M
Tilt switch to prevent wrong weighing results in mobile scales.
(Digital Input-4)
NO
OPEN
CLOS
:
:
:
Not used.
Normally open contact.
Normally closed contact.
52- BUILD
]
SCALE BUILD
Press key or
key again to enter this menu.
Press
key to enter the next sub-block or press
key to go
to the next main block.
[ 521 UNIT
: KG
] M The scale unit
Select NO, g, kg, t, lb, klb, N or kN.
Page 35
[ 522 RANGE
: SING ] M Scale range
SING
2MR
3MR
2MI
3MI
:
:
:
:
:
Single Range
2 x Multi Range
3 x Multi Range
2 x Multi Interval
3 x Multi Interval