18 MG302-EU-EN V2.0 4/11
Meg OHMS
Terminal Voltage
Range
Resolution Accuracy
Test current Short circuit
current
125V (0%~+10%) 0.125~4.000 M
Ω
0.001M
Ω
+(2%+10)
1mA @ load
125k
Ω
≤
1mA
4.001~40.00 M
Ω
0.01M
Ω
+(2%+10)
40.01~400.0 M
Ω
0.1M
Ω
+(4%+5)
400.1~4000 M
Ω
1M
Ω
+(5%+5)
250V (0%~+10%) 0.250~4.000 M
Ω
0.001M
Ω
+(2%+10)
1mA @ load
250k
Ω
≤
1mA
4.001~40.00 M
Ω
0.01M
Ω
+(2%+10)
40.01~400.0 M
Ω
0.1M
Ω
+(3%+5)
400.1~4000 M
Ω
1M
Ω
+(4%+5)
500V (0%~+10%) 0.500~4.000 M
Ω
0.001M
Ω
+(2%+10)
1mA @ load
500k
Ω
≤
1mA
4.001~40.00 M
Ω
0.01M
Ω
+(2%+10)
40.01~400.0 M
Ω
0.1M
Ω
+(2%+5)
400.1~4000 M
Ω
1M
Ω
+(4%+5)
1000V
(0%~+10%)
1.000~4.000 M
Ω
0.001M
Ω
+(3%+10)
1mA @ load
1M
Ω
≤
1mA
4.001~40.00 M
Ω
0.01M
Ω
+(2%+10)
40.01~400.0 M
Ω
0.1M
Ω
+(2%+5)
400.1~4000 M
Ω
1M
Ω
+(4%+5)
Note: Accuracy specifications consist of two elements:
•
(% reading) – This is the accuracy of the measurement circuit.
•
(+ digits) – This is the accuracy of the analog to digital converter.